KNX control elements and application parameters
Application "Fault and alarm messages" - Settings of the individual messages
Product manual 2CKA001473B5342
│
207
Designation of message. The length of the name is limited to 60 characters.
10.19.2 Type of message
Options:
Alarm
Notice
Error
The parameter is used to specify the type of message that is displayed.
10.19.3 Type of alarm
Options:
1 bit
14 bytes
The parameter is used to specify whether the alarm is displayed and sent with or without text.
–
1 bit
: No text is displayed and sent when acknowledging the alarm. The following
supplementary parameters are available:
Text for alarm message
:
Options:
<Text>
The parameter is used to specify the text that is displayed when this message appears. The
length of the text is limited to 60 characters.
Sending 0 at acknowledgement
:
Options:
Deactivated
Activated
The parameter is used to specify whether "0" is sent at acknowledgement.
Acoustic alarm signal
:
Options:
Deactivated
Activated
The parameter is used to specify whether the signal tone specified under the global settings
is played see chapter 10.18 “Application "Fault and alarm messages" - Global settings“ on
page 205.
–
Deactivated
: No acoustic alarm signal. No additional parameters available.
–
Activated
: The signal tone is played at an alarm signal. The following supplementary
parameter is available:
Duration of audio signal [min.]
:
Options:
Setting option from 1 - 60
The parameter is used to specify how long the specified signal tone is to be played (in
minutes).