KNX control elements and application parameters
"Dimmer" control element
Product manual 2CKA001473B5342
│
127
Notice
The parameter can only be set when parameter "Icon type" is set on "User-
defined".
10.3.7 Status control element (icon) is controlled by a separate object
Options:
Deactivated
Activated
An additional 1-bit communication object "Status" is enabled via the parameter.
When the object has been enabled, the status display of the control element indicates the
current status of the object. The feedback object can ensure that the correct status is always
displayed.
If an actuator has a separate feedback object, this additional object can check whether the
actuator has switched. For this the feedback object of the actuator must be connected with the
feedback object of the button via a common group address (Action).
If the status display is not activated via a feedback object, the control element always changes
to the other status when actuated.
10.3.8 Manner of dimming
Options:
Start/stop
Stepwise
Value
–
Start/stop
: When the button is pressed a telegram with the information "dim brighter" or "dim
darker" is sent. When the button is released a telegram with the information "stop dimming"
is sent.
Brightness change [%]
:
Options:
Setting option in % (different values)
The parameter is used to specify in which step widths to dim.
Telegram is repeated every [sec.]
:
Options:
Setting option from 0.25 - 1.25 seconds
The parameter is used to specify the space of time between two dimming telegrams.
10.3.9 Enable 1-bit communication object "Disable"
Options:
Deactivated
Activated
There is the option of temporarily disabling the function via an additional communication object
"Disable".