background image

SB-170-9 RUS

93

SB-170-9

25

5.4.2 CM-SW-01

Standard for all CSW105 compressors
The compressor module integrates the entire electronic

periphery of the compressor: It allows monitoring the

essential operating parameters of the compressor: mo-

tor and discharge gas temperature, phase and rotation

direction monitoring, oil supply and application limits

and thus protects the compressor from operation under

critical conditions. For further information, see Tech-

nical Information ST-150.

!

!

NOTICE

The compressor module may be damaged or

fail!

Never apply any voltage to the terminals of CN7

to CN12 – not even for test purposes!

The voltage applied to the terminals of CN13

must not exceed 10 V!

The voltage applied to terminal 3 of CN14 must

not exceed 24 V! Do no apply voltage to the

other terminals!

The following components are completely installed and

wired in the state of delivery:
• Slider position indicator.
• Oil monitoring (OLC-D1).
• Solenoid valves for capacity control and V

i

.

• Discharge gas temperature sensor.
• Low pressure and high pressure transmitter.
Modification to these components or their wiring is not

required and should not be done without consulting

BITZER.
The following components are not installed and wired in

the state of delivery and need to be connected:
• Motor temperature monitoring (PTC sensor in motor

winding).

• Phase monitoring (in case of a phase failure or inad-

missibly high phase asymmetry).

The compressor module internally supplies voltage to

the peripheral devices (solenoid valves, oil monitoring

device and slider position indicator) and to the terminal

strips CN7 to CN12.
Please refer to the Technical Information ST-150 for in-

formation on all connections.

5.4.3 SE-i1
This protection device with extended monitoring func-

tions can be used as an option for all HS.53 .. HS.85

compressors and CSH and CSW compressors.
Monitoring functions:
• Temperature monitoring.
• Monitoring of the PTC control circuit to detect any

short-circuit or line break/sensor failure.

• Rotation direction monitoring.
• Monitoring of phase failure and asymmetry.
• Monitoring of the maximum cycling rate.
For further information, see Technical Information

CT-110.

5.4.4 SE-E2
Optional protection device for operation with frequency

inverter and soft starter (for a ramp time shorter than

1 s).
• Dimensions and integration in the control identical to

SE-E1.

• Suitable for all CS. compressors.
• Monitoring functions are basically identical to those

of SE-E1. However, the SE-E2 monitors phase fail-

ure during the entire running time of the compressor.

For further information, see Technical Information

ST-122.

5.4.5 Monitoring of the oil circuit
• For short circuits without liquid injection (LI) for addi-

tional cooling and for small system volume and small

refrigerant charge: Indirect monitoring with oil tem-

perature sensor (standard)

!

!

NOTICE

Lack of oil leads to a too high increase in tem-

perature.

Risk of damage to the compressor!

• For circuits with liquid injection (LI) for additional

cooling and / or for great system volume as well as

parallel compounding: Monitor oil level directly with

opto-electronic oil level monitoring (option), see

chapter Opto-electronic oil level monitoring OLC-D1-

S, page 26. The connection is on the compressor

housing, see chapter Connections and dimensional

drawings, page 14, position 8.

SB-170-9

93

5.4.6 Dispositifs de sécurité pour la limitation de

pression (HP et LP)

• Nécessaires pour sécuriser le champ d’application

du compresseur de manière à éviter que des condi-

tions d’utilisation inadmissibles ne surviennent.

• Il ne faut en aucun cas les raccorder au raccord de

maintenance de la vanne d’arrêt !

• Régler les pressions d’enclenchement et de déclen-

chement conformément aux limites d’application et

les contrôler exactement au moyen d’un test.

5.4.7 Chauffage d’huile
Le chauffage d'huile garantit le pouvoir lubrifiant de

l'huile même après des temps d'arrêt prolongés. Il per-

met d'éviter un enrichissement de fluide frigorigène

dans l'huile et donc une réduction de la viscosité.
L'huile doit être chauffée pendant l'arrêt du compres-

seur en cas :
• D'installation en extérieur du compresseur,
• D'arrêts prolongés,
• D'un grand volume de fluide frigorigène,
• De risque de condensation de liquide frigorigène

dans le compresseur.

Les connexions se font conformément aux Informations

techniques KT-150.

Isoler le séparateur d'huile
L'opération à faibles températures ambiantes ou tem-

pératures élevées côté haute pression pendant les

temps d'arrêt (p. ex. pour les pompes à chaleur) néces-

site une isolation additionnelle du séparateur d'huile.

6 Mettre en service
Avant de sortir de l'usine, le compresseur est soigneu-

sement séché, son étanchéité contrôlée et il est rempli

de gaz de protection (N

2

).

DANGER

Danger d'explosion !

Le compresseur ne doit en aucun cas être mis

sous pression avec de l'oxygène (O

2

) ou

d'autres gaz techniques !

AVERTISSEMENT

Danger d'éclatement !

Risque de décalage critique de la limite d'inflam-

mabilité du fluide frigorigène en cas de surpres-

sion.

Ne pas mélanger de fluide frigorigène (par ex.

en tant qu'indicateur de fuite) au gaz d'essai (N

2

ou air).

Pollution en cas de fuite ou de dégonflement !

!

!

AVIS

Danger d'oxydation de l'huile !

Utiliser de préférence du nitrogène déshydraté

(N

2

) pour contrôler la résistance à la pression et

l'étanchéité de l'ensemble de l'installation.

En cas d'utilisation d'air séché : Mettre le com-

presseur hors-circuit – obligatoirement maintenir

les vannes d'arrêt fermée.

6.1 Contrôler la résistance à la pression
Contrôler le circuit frigorifique (groupe assemblé) selon

la norme EN378-2 ou toute autre norme de sécurité

équivalente également valable. Le compresseur a déjà

fait l'objet avant sa sortie d'usine d'un contrôle de sa ré-

sistance à la pression. Un simple essai d'étanchéité est

donc suffisant, voir chapitre Contrôler l'étanchéité, page

94. Si toutefois, l'ensemble du groupe assemblé doit

subir un contrôle de sa résistance à la pression :

DANGER

Danger d'éclatement dû à une trop grande pres-

sion !

La pression d'essai ne doit pas dépasser la

pression maximale admissible !

Pression d'essai : 1,1 fois la pression de service

maximale admissible (voir plaque de désigna-

tion). Différencier les côtés de haute et de

basse pression !

5.4.7  Подогреватель масла
Подогреватель масла обеспечивает смазывающую 

способность масла даже после длительных периодов 

простоя компрессора. Он предохраняет от повышения 

концентрации хладагента в масле и таким образом от 

снижения его вязкости.
Подогреватель масла должен быть включен в периоды 

простоя компрессора, при: 
•  установке компрессора вне помещения,
•  длительных периодах простоя,
•  большой заправке хладагентом,
•  опасности конденсации хладагента в компрессоре.
Подключение осуществляйте в соответствии с 

технической информацией КТ-150.

Изоляция маслоотделителя
При эксплуатации при низких температурах окружающей 

среды или при высоких температурах на стороне 

высокого давления во время останова (например, 

тепловые насосы) требуется дополнительная изоляция 

маслоотделителя.

5.4.6   Предохранительные устройства для 

ограничения давления (HP и LP)

•   Необходимы для ограничения области применения 

компрессора, для исключения недопустимых рабочих 

условий.

•   Ни в коем случае не подключать реле к сервисному 

штуцеру на запорном клапане!

•   Установите давление замыкания и размыкания в 

соответствии с областью применения и выполните 

тестовые проверки, чтобы точно их подтвердить.

6  Ввод в эксплуатацию
Компрессор на заводе-изготовителе уже тщательно 

высушен, испытан на плотность и заполнен защитным 

газом (N

2

).

ОПАСНОСТЬ

Возможен взрыв!

Ни в коем случае не допускается проводить 

испытания компрессора кислородом (О

2

) или 

другими промышленными газами!

ПРЕДУПРЕЖДЕНИЕ

Опасность разрыва!

Может произойти опасное снижение точки 

воспламенения хладагента при высоком 

давлении!

Никогда не добавляйте хладагент в газ для 

испытания (N

2

 или воздух) – например, как 

индикатор утечек.

Возможны загрязнения окружающей среды 

утечками хладагента при испытании контура и 

при откачке испытательного газа!

ВНИМАНИЕ

Опасность окисления масла!

Испытание на прочность и плотность всей 

системы предпочтительно проводить сухим 

азотом (N

2

). 

При использовании сухого воздуха: 

компрессор должен быть отсечен от системы - 

держите запорные клапаны закрытыми.

6.1  Испытание давлением на прочность 
Испытайте смонтированный холодильный контур 

согласно указанию, EN 378-2 (или другому 

действующему стандарту безопасности). Компрессор 

уже был испытан на прочность давлением на 

заводе-изготовителе. Поэтому достаточно провести 

испытание на плотность, смотрите главу Испытание 

на плотность, страница 27. Однако, если вся система 

испытывается давлением на прочность:

ОПАСНОСТЬ

Опасность разрыва из-за высокого давления!

Пробное давление не должно превышать 

максимально допустимых значений!

Пробное давление: 1,1*максимально 

допустимое рабочее давление (смотрите 

заводскую табличку). При этом разделяйте 

сторону высокого и низкого давления!

SB-170-9

26

Opto-electronic oil level monitoring OLC-D1-S
The OLC-D1-S is an opto-electronic proximity sensor

that monitors the oil level with infrared light. Depending

on the mounting position and electrical connection, the

same unit can be used for monitoring the minimum and

maximum oil levels.
The monitoring device comprises two parts: a prism

unit and an opto-electronic unit.
• The prism unit – a glass cone is mounted directly

into the compressor housing.

• The opto-electronic unit is designated as OLC-D1. It

is not directly connected to the refrigerating circuit. It

is screwed into the prism unit and integrated in the

system's control logic. No external control device is

required.

Delivery in a pre-setup state
If the prism unit of the OLC-D1-S has been ordered

pre-assembled, the compressor will have already been

tested as a whole in the factory for strength pressure

and tightness. In this case, it will only be necessary to

screw in the opto-electronic unit and to connect it elec-

trically (see Technical Information ST-130). Sub-

sequent tightness testing will not be required in this

case.
When retrofitting, both prism and electronic unit must

be mounted. For a detailed mounting description,

please see Technical Information ST-130.

5.4.6 Safety devices for pressure limiting (HP and LP)
• These safety devices are required for securing the

compressor's application range in order to avoid un-

acceptable operating conditions.

• Do not connect any safety devices to the mainten-

ance connection of the shut-off valve!

• Set cut-in and cut-out pressures according to the ap-

plication limits and perform a test to exactly check

them.

5.4.7 Oil heater
The oil heater ensures the lubricity of the oil even after

long standstill periods. It prevents increased refrigerant

concentration in the oil and therefore reduction of vis-

cosity.
The oil heater must be operated while the compressor

is at standstill in case of
• outdoor installation of the compressor,
• long shut-off periods,
• high refrigerant charge,
• possible refrigerant condensation in the compressor.
Connection according to Technical Information KT-150.

Isolating the oil separator
Operating at low ambient temperatures or with high

temperatures on the high-pressure side during stand-

still (e.g. for heat pumps) requires additional isolation of

the oil separator.

6 Commissioning
The compressor has been carefully dried, checked for

tightness and filled with a holding charge (N

2

) before

leaving the factory.

DANGER

Risk of explosion!

Never pressurize the compressor with oxygen

(O

2

) or other industrial gases!

WARNING

Risk of bursting!

A critical shift of the refrigerant ignition limit is

possible in case of excess pressure.

Do not add a refrigerant (e.g. as a leak indic-

ator) to the test gas (N

2

 or air).

Environmental pollution in case of leakage and

when deflating!

!

!

NOTICE

Risk of oil oxidation!

Check the entire system for strength pressure

and tightness, preferably using dried nitrogen

(N

2

).

When using dried air: Remove the compressor

from the circuit – make sure to keep the shut-off

valves closed.

SB-170-9

26

Opto-electronic oil level monitoring OLC-D1-S
The OLC-D1-S is an opto-electronic proximity sensor

that monitors the oil level with infrared light. Depending

on the mounting position and electrical connection, the

same unit can be used for monitoring the minimum and

maximum oil levels.
The monitoring device comprises two parts: a prism

unit and an opto-electronic unit.
• The prism unit – a glass cone is mounted directly

into the compressor housing.

• The opto-electronic unit is designated as OLC-D1. It

is not directly connected to the refrigerating circuit. It

is screwed into the prism unit and integrated in the

system's control logic. No external control device is

required.

Delivery in a pre-setup state
If the prism unit of the OLC-D1-S has been ordered

pre-assembled, the compressor will have already been

tested as a whole in the factory for strength pressure

and tightness. In this case, it will only be necessary to

screw in the opto-electronic unit and to connect it elec-

trically (see Technical Information ST-130). Sub-

sequent tightness testing will not be required in this

case.
When retrofitting, both prism and electronic unit must

be mounted. For a detailed mounting description,

please see Technical Information ST-130.

5.4.6 Safety devices for pressure limiting (HP and LP)
• These safety devices are required for securing the

compressor's application range in order to avoid un-

acceptable operating conditions.

• Do not connect any safety devices to the mainten-

ance connection of the shut-off valve!

• Set cut-in and cut-out pressures according to the ap-

plication limits and perform a test to exactly check

them.

5.4.7 Oil heater
The oil heater ensures the lubricity of the oil even after

long standstill periods. It prevents increased refrigerant

concentration in the oil and therefore reduction of vis-

cosity.
The oil heater must be operated while the compressor

is at standstill in case of
• outdoor installation of the compressor,
• long shut-off periods,
• high refrigerant charge,
• possible refrigerant condensation in the compressor.
Connection according to Technical Information KT-150.

Isolating the oil separator
Operating at low ambient temperatures or with high

temperatures on the high-pressure side during stand-

still (e.g. for heat pumps) requires additional isolation of

the oil separator.

6 Commissioning
The compressor has been carefully dried, checked for

tightness and filled with a holding charge (N

2

) before

leaving the factory.

DANGER

Risk of explosion!

Never pressurize the compressor with oxygen

(O

2

) or other industrial gases!

WARNING

Risk of bursting!

A critical shift of the refrigerant ignition limit is

possible in case of excess pressure.

Do not add a refrigerant (e.g. as a leak indic-

ator) to the test gas (N

2

 or air).

Environmental pollution in case of leakage and

when deflating!

!

!

NOTICE

Risk of oil oxidation!

Check the entire system for strength pressure

and tightness, preferably using dried nitrogen

(N

2

).

When using dried air: Remove the compressor

from the circuit – make sure to keep the shut-off

valves closed.

SB-170-9

26

Opto-electronic oil level monitoring OLC-D1-S
The OLC-D1-S is an opto-electronic proximity sensor

that monitors the oil level with infrared light. Depending

on the mounting position and electrical connection, the

same unit can be used for monitoring the minimum and

maximum oil levels.
The monitoring device comprises two parts: a prism

unit and an opto-electronic unit.
• The prism unit – a glass cone is mounted directly

into the compressor housing.

• The opto-electronic unit is designated as OLC-D1. It

is not directly connected to the refrigerating circuit. It

is screwed into the prism unit and integrated in the

system's control logic. No external control device is

required.

Delivery in a pre-setup state
If the prism unit of the OLC-D1-S has been ordered

pre-assembled, the compressor will have already been

tested as a whole in the factory for strength pressure

and tightness. In this case, it will only be necessary to

screw in the opto-electronic unit and to connect it elec-

trically (see Technical Information ST-130). Sub-

sequent tightness testing will not be required in this

case.
When retrofitting, both prism and electronic unit must

be mounted. For a detailed mounting description,

please see Technical Information ST-130.

5.4.6 Safety devices for pressure limiting (HP and LP)
• These safety devices are required for securing the

compressor's application range in order to avoid un-

acceptable operating conditions.

• Do not connect any safety devices to the mainten-

ance connection of the shut-off valve!

• Set cut-in and cut-out pressures according to the ap-

plication limits and perform a test to exactly check

them.

5.4.7 Oil heater
The oil heater ensures the lubricity of the oil even after

long standstill periods. It prevents increased refrigerant

concentration in the oil and therefore reduction of vis-

cosity.
The oil heater must be operated while the compressor

is at standstill in case of
• outdoor installation of the compressor,
• long shut-off periods,
• high refrigerant charge,
• possible refrigerant condensation in the compressor.
Connection according to Technical Information KT-150.

Isolating the oil separator
Operating at low ambient temperatures or with high

temperatures on the high-pressure side during stand-

still (e.g. for heat pumps) requires additional isolation of

the oil separator.

6 Commissioning
The compressor has been carefully dried, checked for

tightness and filled with a holding charge (N

2

) before

leaving the factory.

DANGER

Risk of explosion!

Never pressurize the compressor with oxygen

(O

2

) or other industrial gases!

WARNING

Risk of bursting!

A critical shift of the refrigerant ignition limit is

possible in case of excess pressure.

Do not add a refrigerant (e.g. as a leak indic-

ator) to the test gas (N

2

 or air).

Environmental pollution in case of leakage and

when deflating!

!

!

NOTICE

Risk of oil oxidation!

Check the entire system for strength pressure

and tightness, preferably using dried nitrogen

(N

2

).

When using dried air: Remove the compressor

from the circuit – make sure to keep the shut-off

valves closed.

SB-170-9

27

6.1 Checking pressure strength
Check the refrigerant circuit (assembly) according to

EN378-2 (or other applicable equivalent safety stand-

ards). The compressor had been already tested in the

factory for strength pressure. A tightness test is there-

fore sufficient, see chapter Checking tightness, page

27. If you still wish to perform a strength pressure test

for the entire assembly:

DANGER

Risk of bursting due to excessive pressure!

The pressure applied during the test must never

exceed the maximum permitted values!

Test pressure: 1.1-fold of the maximum allow-

able pressure (see name plate). Make a distinc-

tion between the high-pressure and low-pres-

sure sides!

6.2 Checking tightness
Check the refrigerant circuit (assembly) for tightness,

as a whole or in parts, according to EN378-2 (or other

applicable equivalent safety standards). For this, create

an excess pressure, preferably using dried nitrogen.
Observe test pressures and safety reference, see

chapter Checking pressure strength, page 27.

6.3 Evacuation
• Switch on the oil heater.
• Open all shut-off valves and solenoid valves.
• Use a vacuum pump to evacuate the entire system,

including the compressor, on the suction side and

the high-pressure side.
With the vacuum pump shut off, a "standing vacuum"

lower than 1.5 mbar must be achieved.

• Repeat the operation several times if necessary.

!

!

NOTICE

Risk of damage to the motor and compressor!

Do not start the compressor while it is in a va-

cuum!

Do not apply any voltage, not even for testing!

6.4 Charging refrigerant
Use only permitted refrigerants, see see chapter Ap-

plication ranges, page 5.

DANGER

Risk of bursting of components and pipelines

due to hydraulic excess pressure while feeding

liquid.

Serious injuries are possible.

Avoid overcharging the system with refrigerant

under all circumstances!

WARNING

Risk of bursting due to counterfeit refrigerants!

Serious injuries are possible!

Purchase refrigerants only from reputable man-

ufacturers and reliable distributors!

!

!

NOTICE

Risk of wet operation during liquid feeding!

Measure out extremely precise quantities!

Maintain the discharge gas temperature at least

20 K above the condensing temperature.

➙ Before charging with refrigerant:
➙ Do not switch on the compressor!
➙ Switch on the oil heater.
➙ Check the oil level in the compressor.
• Fill liquid refrigerant directly into the condenser or re-

ceiver; on systems with flooded evaporator, maybe

directly into the evaporator.

• Blends must be taken out of the charging cylinder as

a solid liquid.

• After commissioning, it may be necessary to add re-

frigerant: While the compressor is running, charge

with refrigerant on the suction side, preferably at the

evaporator inlet. Blends must be taken out of the

charging cylinder as a solid liquid.

Summary of Contents for CSH6553-35Y

Page 1: ...C control circuit to detect any short circuit or line break sensor failure Rotation direction monitoring Monitoring of phase failure and asymmetry Monitoring of the maximum cycling rate For further in...

Page 2: ...r les 2 s Effectuer correctement les raccordements Toute erreur d arrangement des raccords lectriques aboutit un court circuit Information Les contacteurs r seau et triangles doivent tre calcul s au m...

Page 3: ...lure and asymmetry Monitoring of the maximum cycling rate For further information see Technical Information CT 110 5 4 4 SE E2 Optional protection device for operation with frequency inverter and soft...

Page 4: ...agement de l isolant et de d faillance du moteur Il ne faut surtout pas r p ter l essai de haute tension de la m me mani re Un nouvel essai de haute tension ne doit tre r alis qu une tension alternati...

Page 5: ...nd for small system volume and small refrigerant charge Indirect monitoring with oil tem perature sensor standard NOTICE Lack of oil leads to a too high increase in tem perature Risk of damage to the...

Page 6: ...I liquid injection The economiser of the compressor models CSW65 to CSW105 and CSH76 to CSH96 is only active at full load These compressors have no connections for addi tional cooling For production r...

Page 7: ...onitoring Monitoring of the PTC control circuit to detect any short circuit or line break sensor failure Rotation direction monitoring Monitoring of phase failure and asymmetry Monitoring of the maxim...

Page 8: ...retard de temps entre la mise en route du compres seur d un c t et de l autre la commutation entre l op ration en toile et celle en triangle ne doit pas d passer les 2 s Effectuer correctement les ra...

Page 9: ...cally identical to those of SE E1 However the SE E2 monitors phase fail ure during the entire running time of the compressor For further information see Technical Information ST 122 5 4 5 Monitoring o...

Page 10: ...ment les raccordements Toute erreur d arrangement des raccords lectriques aboutit un court circuit Information Les contacteurs r seau et triangles doivent tre calcul s au moins 60 du courant de servic...

Page 11: ...tem perature sensor standard NOTICE Lack of oil leads to a too high increase in tem perature Risk of damage to the compressor For circuits with liquid injection LI for additional cooling and or for g...

Page 12: ...tension de la m me mani re Un nouvel essai de haute tension ne doit tre r alis qu une tension alternative max de 1000 V CA SB 170 9 12 Mount pipelines in such a way that the compressor is protected f...

Page 13: ...phase failure and asymmetry Monitoring of the maximum cycling rate For further information see Technical Information CT 110 5 4 4 SE E2 Optional protection device for operation with frequency inverte...

Page 14: ...contacteurs moteur 1er contacteur PW 1 60 du courant de ser vice max 2 me contacteur PW 2 60 du courant de ser vice max Moteur toile triangle Le retard de temps entre la mise en route du compres seur...

Page 15: ...monitoring Monitoring of the PTC control circuit to detect any short circuit or line break sensor failure Rotation direction monitoring Monitoring of phase failure and asymmetry Monitoring of the maxi...

Page 16: ...partiel contacteur K1 Raccords 1 2 3 2 me bobinage partiel contacteur K2 Raccords 7 8 9 Partage de bobinage 50 50 R partition des contacteurs moteur 1er contacteur PW 1 60 du courant de ser vice max 2...

Page 17: ...control circuit to detect any short circuit or line break sensor failure Rotation direction monitoring Monitoring of phase failure and asymmetry Monitoring of the maximum cycling rate For further info...

Page 18: ...r K1 Raccords 1 2 3 2 me bobinage partiel contacteur K2 Raccords 7 8 9 Partage de bobinage 50 50 R partition des contacteurs moteur 1er contacteur PW 1 60 du courant de ser vice max 2 me contacteur PW...

Page 19: ...Monitoring functions Temperature monitoring Monitoring of the PTC control circuit to detect any short circuit or line break sensor failure Rotation direction monitoring Monitoring of phase failure and...

Page 20: ...age partiel contacteur K2 Raccords 7 8 9 Partage de bobinage 50 50 R partition des contacteurs moteur 1er contacteur PW 1 60 du courant de ser vice max 2 me contacteur PW 2 60 du courant de ser vice m...

Page 21: ...circuit to detect any short circuit or line break sensor failure Rotation direction monitoring Monitoring of phase failure and asymmetry Monitoring of the maximum cycling rate For further information...

Page 22: ...e des bobinages par tiels 1er bobinage partiel contacteur K1 Raccords 1 2 3 2 me bobinage partiel contacteur K2 Raccords 7 8 9 Partage de bobinage 50 50 R partition des contacteurs moteur 1er contacte...

Page 23: ...e compressor For circuits with liquid injection LI for additional cooling and or for great system volume as well as parallel compounding Monitor oil level directly with opto electronic oil level monit...

Page 24: ...nded ro tation direction The compressor series CS 65 CS 75 CS 85 CSH76 and CSH86 and are equipped by default with part wind ing motors PW in wiring Star delta motors Y are also available as an option...

Page 25: ...connection is on the compressor housing see chapter Connections and dimensional drawings page 14 position 8 SB 170 9 25 5 4 2 CM SW 01 Standard for all CSW105 compressors The compressor module integra...

Page 26: ...nsor that monitors the oil level with infrared light Depending on the mounting position and electrical connection the same unit can be used for monitoring the minimum and maximum oil levels The monito...

Page 27: ...r circuits with liquid injection LI for additional cooling and or for great system volume as well as parallel compounding Monitor oil level directly with opto electronic oil level monitoring option se...

Page 28: ...sor start Oil level between the middle of the lower sight glass and the upper area of the upper sight glass During compressor start oil temperature must be at least 20 C and 20 K above ambient tempera...

Page 29: ...echnical Information ST 122 5 4 5 Monitoring of the oil circuit For short circuits without liquid injection LI for addi tional cooling and for small system volume and small refrigerant charge Indirect...

Page 30: ...d requirements must be ensured by the control logic Desirable minimum running time 5 minutes Switching the compressor off When using a star delta motor shut it off from the 25 CR stage Minimum standst...

Page 31: ...h liquid injection LI for additional cooling and or for great system volume as well as parallel compounding Monitor oil level directly with opto electronic oil level monitoring option see chapter Opto...

Page 32: ...rm ment aux normes UL984 ou UL60335 2 34 pour la version UL AVIS Risque d endommagement de l isolant et de d faillance du moteur Il ne faut surtout pas r p ter l essai de haute tension de la m me mani...

Page 33: ...ure during the entire running time of the compressor For further information see Technical Information ST 122 5 4 5 Monitoring of the oil circuit For short circuits without liquid injection LI for ad...

Page 34: ...ne doit pas d passer les 2 s Effectuer correctement les raccordements Toute erreur d arrangement des raccords lectriques aboutit un court circuit Information Les contacteurs r seau et triangles doiven...

Page 35: ...inverter and soft starter for a ramp time shorter than 1 s Dimensions and integration in the control identical to SE E1 Suitable for all CS compressors Monitoring functions are basically identical to...

Page 36: ...ur toile triangle Le retard de temps entre la mise en route du compres seur d un c t et de l autre la commutation entre l op ration en toile et celle en triangle ne doit pas d passer les 2 s Effectuer...

Page 37: ...ard NOTICE Lack of oil leads to a too high increase in tem perature Risk of damage to the compressor For circuits with liquid injection LI for additional cooling and or for great system volume as well...

Page 38: ...aux normes UL984 ou UL60335 2 34 pour la version UL AVIS Risque d endommagement de l isolant et de d faillance du moteur Il ne faut surtout pas r p ter l essai de haute tension de la m me mani re Un...

Page 39: ...8 SB 170 9 39 3 1 Economiser und Zusatzk hlung Die Verdichter CSH65 bis CSH95 haben einen Econo miseranschluss ECO der im ganzen Regelbereich der Leistungsregelung aktiv ist Sie haben ebenfalls An sch...

Page 40: ...7 8 9 Partage de bobinage 50 50 R partition des contacteurs moteur 1er contacteur PW 1 60 du courant de ser vice max 2 me contacteur PW 2 60 du courant de ser vice max Moteur toile triangle Le retard...

Page 41: ...asymmetry Monitoring of the maximum cycling rate For further information see Technical Information CT 110 5 4 4 SE E2 Optional protection device for operation with frequency inverter and soft starter...

Page 42: ...tre calcul s au moins 60 du courant de service max le contacteur toile 33 5 3 Essai de haute tension test de r sistance d isolation Les compresseurs ont d j t soumis avant leur sortie d usine un essai...

Page 43: ...requency inverter and soft starter for a ramp time shorter than 1 s Dimensions and integration in the control identical to SE E1 Suitable for all CS compressors Monitoring functions are basically iden...

Page 44: ...Il ne faut surtout pas r p ter l essai de haute tension de la m me mani re Un nouvel essai de haute tension ne doit tre r alis qu une tension alternative max de 1000 V CA SB 170 9 44 4 3 Rohrleitunge...

Page 45: ...erature Risk of damage to the compressor For circuits with liquid injection LI for additional cooling and or for great system volume as well as parallel compounding Monitor oil level directly with opt...

Page 46: ...er vice max Moteur toile triangle Le retard de temps entre la mise en route du compres seur d un c t et de l autre la commutation entre l op ration en toile et celle en triangle ne doit pas d passer l...

Page 47: ...the PTC control circuit to detect any short circuit or line break sensor failure Rotation direction monitoring Monitoring of phase failure and asymmetry Monitoring of the maximum cycling rate For fur...

Page 48: ...bobinage 50 50 R partition des contacteurs moteur 1er contacteur PW 1 60 du courant de ser vice max 2 me contacteur PW 2 60 du courant de ser vice max Moteur toile triangle Le retard de temps entre l...

Page 49: ...option for all HS 53 HS 85 compressors and CSH and CSW compressors Monitoring functions Temperature monitoring Monitoring of the PTC control circuit to detect any short circuit or line break sensor fa...

Page 50: ...contacteurs moteur 1er contacteur PW 1 60 du courant de ser vice max 2 me contacteur PW 2 60 du courant de ser vice max Moteur toile triangle Le retard de temps entre la mise en route du compres seur...

Page 51: ...53 HS 85 compressors and CSH and CSW compressors Monitoring functions Temperature monitoring Monitoring of the PTC control circuit to detect any short circuit or line break sensor failure Rotation di...

Page 52: ...teur K2 Raccords 7 8 9 Partage de bobinage 50 50 R partition des contacteurs moteur 1er contacteur PW 1 60 du courant de ser vice max 2 me contacteur PW 2 60 du courant de ser vice max Moteur toile tr...

Page 53: ...and CSW compressors Monitoring functions Temperature monitoring Monitoring of the PTC control circuit to detect any short circuit or line break sensor failure Rotation direction monitoring Monitoring...

Page 54: ...teurs moteur 1er contacteur PW 1 60 du courant de ser vice max 2 me contacteur PW 2 60 du courant de ser vice max Moteur toile triangle Le retard de temps entre la mise en route du compres seur d un c...

Page 55: ...monitoring func tions can be used as an option for all HS 53 HS 85 compressors and CSH and CSW compressors Monitoring functions Temperature monitoring Monitoring of the PTC control circuit to detect a...

Page 56: ...la m me mani re Un nouvel essai de haute tension ne doit tre r alis qu une tension alternative max de 1000 V CA SB 170 9 56 Anschlusspositionen 1 Hochdruckanschluss HP 2 Zus tzlicher Hochdruckanschlu...

Page 57: ...rectly with opto electronic oil level monitoring option see chapter Opto electronic oil level monitoring OLC D1 S page 26 The connection is on the compressor housing see chapter Connections and dimens...

Page 58: ...B 170 9 58 5 4 2 CM SW 01 Standard bei allen CSW105 Verdichtern Das Verdichtermodul integriert die gesamte elektroni sche Peripherie des Verdichters Es erlaubt die ber wachung der wesentlichen Betrieb...

Page 59: ...liquid injection LI for additional cooling and or for great system volume as well as parallel compounding Monitor oil level directly with opto electronic oil level monitoring option see chapter Opto e...

Page 60: ...60 6 In Betrieb nehmen Der Verdichter ist ab Werk sorgf ltig getrocknet auf Dichtheit gepr ft und mit Schutzgas N2 bef llt GEFAHR Explosionsgefahr Verdichter keinesfalls mit Sauerstoff O2 oder anderen...

Page 61: ...e chapter Opto electronic oil level monitoring OLC D1 S page 26 The connection is on the compressor housing see chapter Connections and dimensional drawings page 14 position 8 SB 170 9 61 Fl ssiges K...

Page 62: ...e haute tension ne doit tre r alis qu une tension alternative max de 1000 V CA SB 170 9 62 6 6 2 Schmierung lkontrolle Schmierung des Verdichters unmittelbar nach dem Verdichteranlauf pr fen Das lnive...

Page 63: ...ption see chapter Opto electronic oil level monitoring OLC D1 S page 26 The connection is on the compressor housing see chapter Connections and dimensional drawings page 14 position 8 SB 170 9 63 Umsc...

Page 64: ...Wartung Herstellerdokumentation der eingesetzten Bauteile be achten 8 1 lwechsel HINWEIS Verdichterschaden durch zersetztes Ester l Feuchtigkeit wird im Ester l chemisch gebun den und kann durch Evaku...

Page 65: ...charge Indirect monitoring with oil tem perature sensor standard NOTICE Lack of oil leads to a too high increase in tem perature Risk of damage to the compressor For circuits with liquid injection LI...

Page 66: ...calcul s au moins 60 du courant de service max le contacteur toile 33 5 3 Essai de haute tension test de r sistance d isolation Les compresseurs ont d j t soumis avant leur sortie d usine un essai de...

Page 67: ...l HS 53 HS 85 compressors and CSH and CSW compressors Monitoring functions Temperature monitoring Monitoring of the PTC control circuit to detect any short circuit or line break sensor failure Rotatio...

Page 68: ...r sistance d isolation Les compresseurs ont d j t soumis avant leur sortie d usine un essai de haute tension conform ment la norme EN12693 ou conform ment aux normes UL984 ou UL60335 2 34 pour la ver...

Page 69: ...quency inverter and soft starter for a ramp time shorter than 1 s Dimensions and integration in the control identical to SE E1 Suitable for all CS compressors Monitoring functions are basically identi...

Page 70: ...ty reference to avoid a potentially hazard ous situation which could result in death or seri ous injury DANGER Safety reference to avoid an imminently hazard ous situation which may result in death or...

Page 71: ...applied to the terminals of CN13 must not exceed 10 V The voltage applied to terminal 3 of CN14 must not exceed 24 V Do no apply voltage to the other terminals 3 Application ranges Permitted refrigera...

Page 72: ...the compressor An adhesive label show ing this warning sign is enclosed with the Oper ating Instructions Refrigerant burning in the terminal box may only hap pen if several very rare errors occur at...

Page 73: ...example of the CSH85 CSH compressors Weight kg Centre of gravity X mm Centre of gravity Y mm CSH6553 35Y 314 89 22 CSH6553 50 Y 322 100 22 CSH6563 40Y 314 107 22 CSH6563 60 Y 322 120 22 CSH6583 50Y 36...

Page 74: ...83 100 Y 550 102 25 CSH7593 90Y 530 111 25 CSH7593 110 Y 560 123 25 CSH7673 70Y 520 120 25 CSH7683 80Y 530 90 25 CSH7693 90Y 535 111 25 CSH8553 80Y 830 103 22 CSH8553 110 Y 840 115 22 CSH8563 90Y 830...

Page 75: ...s l axe longitudinal du bateau peut tre n ces saire voir figure 3 page 76 SB 170 9 75 Compresseurs CSW Poids kg Centre de gravit X mm Centre de gravit Y mm CSW6583 40Y 360 34 22 CSW6583 50 Y 365 39 22...

Page 76: ...l du bateau et soit horizontalement par rapport au niveau d eau soit pench de 10 dans la direction longitudinale du compresseur avec le moteur vers le bas Pr requis Le niveau d huile reste dans la zon...

Page 77: ...ismount the pipe connections and the bushes When turning or mounting shut off valves NOTICE Risk of damage to the compressor Tighten screws crosswise in at least 2 steps to the prescribed tightening t...

Page 78: ...as 4 stage regulation without any rebuild ing of the compressor The only difference in the oper ating mode is the activation of the solenoid valves The capacity control of CSW105 compressors is auto m...

Page 79: ...tion de la puissance CR 4 tages CAP Puissance frigorifique CAP Faire cro tre la puissance frigorifique CAP Faire d cro tre la puissance frigorifique CAP Puissance frigorifique constante Vanne magn tiq...

Page 80: ...eur PW 1 60 du courant de ser vice max 2 me contacteur PW 2 60 du courant de ser vice max Moteur toile triangle Le retard de temps entre la mise en route du compres seur d un c t et de l autre la comm...

Page 81: ...TC control circuit to detect any short circuit or line break sensor failure Rotation direction monitoring Monitoring of phase failure and asymmetry Monitoring of the maximum cycling rate For further i...

Page 82: ...cords 1 2 3 2 me bobinage partiel contacteur K2 Raccords 7 8 9 Partage de bobinage 50 50 R partition des contacteurs moteur 1er contacteur PW 1 60 du courant de ser vice max 2 me contacteur PW 2 60 du...

Page 83: ...etect any short circuit or line break sensor failure Rotation direction monitoring Monitoring of phase failure and asymmetry Monitoring of the maximum cycling rate For further information see Technica...

Page 84: ...bobinage partiel contacteur K2 Raccords 7 8 9 Partage de bobinage 50 50 R partition des contacteurs moteur 1er contacteur PW 1 60 du courant de ser vice max 2 me contacteur PW 2 60 du courant de ser v...

Page 85: ...toring Monitoring of the PTC control circuit to detect any short circuit or line break sensor failure Rotation direction monitoring Monitoring of phase failure and asymmetry Monitoring of the maximum...

Page 86: ...s 7 8 9 Partage de bobinage 50 50 R partition des contacteurs moteur 1er contacteur PW 1 60 du courant de ser vice max 2 me contacteur PW 2 60 du courant de ser vice max Moteur toile triangle Le retar...

Page 87: ...circuit or line break sensor failure Rotation direction monitoring Monitoring of phase failure and asymmetry Monitoring of the maximum cycling rate For further information see Technical Information CT...

Page 88: ...cteur PW 1 60 du courant de ser vice max 2 me contacteur PW 2 60 du courant de ser vice max Moteur toile triangle Le retard de temps entre la mise en route du compres seur d un c t et de l autre la co...

Page 89: ...Also earth the compressor housing Connection see position 16 in the dimensional draw ings 5 1 Mains connections When dimensioning motor contactors feed lines and fuses Use the maximum operating curre...

Page 90: ...Les mod les CS 95 CSH96 et CSW105 sont g n rale ment quip s de moteurs toile triangle Y Moteurs bobinage partiel PW M thodes de d marrage D marrage bobinage partiel pour r duire le cou rant de d marra...

Page 91: ...the other terminals The following components are completely installed and wired in the state of delivery Slider position indicator Oil monitoring OLC D1 Solenoid valves for capacity control and Vi Dis...

Page 92: ...pour les faibles volumes d installation et faibles contenance en fluide frigorig ne Contr le indirect au moyen d une sonde de temp rature d huile standard AVIS Un manque d huile aboutit une forte aug...

Page 93: ...onnect it elec trically see Technical Information ST 130 Sub sequent tightness testing will not be required in this case When retrofitting both prism and electronic unit must be mounted For a detailed...

Page 94: ...compressor Fill liquid refrigerant directly into the condenser or re ceiver on systems with flooded evaporator maybe directly into the evaporator Blends must be taken out of the charging cylinder as...

Page 95: ...on rotation test without suction shut off valve Close the solenoid valves on the evaporator and the economiser The pressure changes measured in such a case are much lower than with throttled suc tion...

Page 96: ...arrages par heure Temps de commutation des contacteurs moteur Bobinage partiel 0 5 s toile triangle 1 2 s pour CS 65 CS 75 et CS 85 toile triangle 1 5 2 s pour CS 95 et CSW105 6 6 5 6 6 6 20 K 30 K R4...

Page 97: ...ts prolong s aucune galisation de temp rature ou de pression n est atteinte Le cas ch ant monter une commande par pump down command e en fonction du temps ou de la pression ou un s parateur de liquid...

Page 98: ...rrouillage d terminer et liminer la cause 8 Maintenance Respecter la documentation constructeur des compo sants mont s 8 1 Remplacement de l huile AVIS Endommagement du compresseur d une huile d ester...

Page 99: ...erant but dis pose of it properly Loosen screwed joints or flanges on the compressor valves Remove the compressor from the system use hoisting equipment if necessary 9 3 Disposing of the compressor Dr...

Page 100: ...1000 V CA SB 170 9 100 9 3 liminer le compresseur Vidanger l huile du compresseur L huile us e devra tre recycl e de fa on adapt e Faire r parer le com presseur ou l liminer dans le respect de l envir...

Page 101: ...ter mounting Test changed component for tightness Sight glasses with sealing flange Screw size M8 14 Nm M10 18 Nm Sight glasses with union nut Size AF 1 3 4 12 UN 50 150 Nm 2 1 4 12 UN 65 180 Nm AF wi...

Page 102: ...ngle de phase d cal et donc un blocage du moteur Raccorder les bornes du moteur au couvercle de la bo te de raccordement conform ment aux instructions Tenir compte absolument de l ordre des bobinages...

Page 103: ...cator and to the terminal strips CN7 to CN12 Please refer to the Technical Information ST 150 for in formation on all connections 5 4 3 SE i1 This protection device with extended monitoring func tions...

Page 104: ...9 0 70 31 932 0 Fax 49 0 70 31 932 147 bitzer bitzer de www bitzer de nderungen vorbehalten Subject to change nderungen vorbehalten Toutes modifications r serv es80440806 02 2018 80440806 03 2018 Subj...

Reviews: