www.baldormotion.com
Basic Installation 3-29
MN1943
Unshielded
lengths should
be as short as
possible.
V
W
U
Motor
To earth/ground outer shield, use 360° clamps
connected to backplane.
Optional motor
circuit contactor.
Earth
Connect motor
earth/ground to
protective earth on
drive flange.
Figure 14 - Motor connections - 1.5 A ~ 16 A models
Unshielded
lengths should
be as short as
possible.
V
W
U
Motor
To earth/ground outer shield, use 360° clamps
connected to backplane.
Optional motor
circuit contactor.
Earth
Connect motor
earth/ground to
protective earth on
drive flange.
Figure 15 - Motor connections - 21 A ~ 65 A models
For 1.5 A ~ 16 A models, tightening torque for X17 terminal block connections is 0.5-0.6 N·m
(4.4-5.3 lb-in). The 48 A ~ 65 A models use a spring cage connector. For all models, tightening
torque for the flange mounted PE connection is 2.5 N·m (22.1 lb-in).