www.baldormotion.com
Specifications 8-5
MN1943
8.2.3.3 Rating adjustment when sharing DC bus - 6 A model
Note: A 1.2 mH line reactor must be used when DC bus sharing.
Temperature
Switching
frequency
Maximum AC input supply current (RMS)
frequency
Continuous
3 s
overload
60 s
overload
45 °C
4 kHz
14 A
45 °C
(113 °F)
8 kHz
14 A
(113 F)
16 kHz
7.5 A
21 A
17 A
55 °C
4 kHz
8.4 A
21 A
17 A
55 °C
(131 °F)
8 kHz
8.4 A
(131 F)
16 kHz
4.5 A
Table 11 - Continuous current ratings for 6 A model, sharing DC bus
8.2.3.4 Rating adjustment when sharing DC bus - 10.5 A model
Note: A 0.8 mH line reactor must be used when DC bus sharing.
Temperature
Switching
frequency
Maximum AC input supply current (RMS)
frequency
Continuous
3 s
overload
60 s
overload
45 °C
4 kHz
20 A
45 °C
(113 °F)
8 kHz
18 A
(113 F)
16 kHz
13.5 A
36 A
27 A
55 °C
4 kHz
17 A
36 A
27 A
55 °C
(131 °F)
8 kHz
15 A
(131 F)
16 kHz
9 A
Table 12 - Continuous current ratings for 10.5 A model, sharing DC bus
8.2.3.5 Rating adjustment when sharing DC bus - 16 A model
Note: A 0.8 mH line reactor must be used when DC bus sharing.
Temperature
Switching
frequency
Maximum AC input supply current (RMS)
frequency
Continuous
3 s
overload
60 s
overload
45 °C
4 kHz
22 A
45 °C
(113 °F)
8 kHz
20 A
(113 F)
16 kHz
13.5 A
42 A
33 A
55 °C
4 kHz
18 A
42 A
33 A
55 °C
(131 °F)
8 kHz
17.5 A
(131 F)
16 kHz
10 A
Table 13 - Continuous current ratings for 16 A model, sharing DC bus
Summary of Contents for MotiFlex e100
Page 1: ......
Page 2: ......
Page 60: ...www baldormotion com 3 44 Basic Installation MN1943 ...
Page 102: ...www baldormotion com 5 28 Input Output MN1943 ...
Page 136: ...www baldormotion com 7 8 Troubleshooting MN1943 ...
Page 172: ...www baldormotion com 8 36 Specifications MN1943 ...
Page 188: ...www baldormotion com B 6 Control System MN1943 ...
Page 204: ...www baldormotion com C 16 Mint Keyword Summary MN1943 ...
Page 216: ...Index MN1943 ...
Page 218: ...www baldormotion com Comments MN1943 Thank you for taking the time to help us ...
Page 219: ......
Page 220: ......