www.baldormotion.com
5-14 Input / Output
MN1943
5.3.6 General purpose / status digital output DOUT0
Location
Connector X3, pins 1 & 13
(Mating connector: Weidmüller Minimate B2L 3.5/24 LH)
Name
Status / DOUT0
Description
General purpose opto-isolated digital output
Output current:
100 mA maximum
User supply
28 VDC maximum
Update interval:
1 ms
The optically isolated general purpose / status output is designed to source current from the user
supply as shown in Figure 54. The TLP 127 has a maximum power dissipation of 150 mW at
25
°
C. The maximum saturated voltage across the outputs when active is 1.0 VDC, so it can be
used as a TTL compatible output.
The output includes a self-resetting fuse that operates at approximately 200 mA. The fuse may
take up to 20 seconds to reset after the load has been removed. If the output is used to directly
drive a relay, a suitably rated diode must be fitted across the relay coil, observing the correct
polarity. This is to protect the output from the back-EMF generated by the relay coil when it is
de-energized. The sense of the output can be configured in Mint WorkBench, and its state is
displayed in the Spy window.
DOUT0+
MotiFlex
e
100
TLP 127
DOUT0-
Load
(Relay with
diode shown)
Fuse
User supply
V+
User supply
GND
200mA
220R
+3.3V
13
1
[Error]
‘X3’
Figure 54 - DOUT0 output circuit
By default, DOUT0 is configured as an error status output, which becomes inactive in the event
of an error. When the MotiFlex
e
100 is connected to Mint WorkBench, the active level of the
output can be configured using the Digital I/O tool. Alternatively, the Mint keyword
OUTPUTACTIVELEVEL
can be used in the command window. Other Mint keywords such as
COMPAREOUTPUT
,
GLOBALERROROUTPUT
,
DRIVEENABLEOUTPUT
and
MOTORBRAKEOUTPUT
(see section 3.7.6) can also be used in the command window. The state of the digital output can
be viewed using the Mint WorkBench Spy window’s Axis tab. See the Mint help file for details.
13
1
Summary of Contents for MotiFlex e100
Page 1: ......
Page 2: ......
Page 60: ...www baldormotion com 3 44 Basic Installation MN1943 ...
Page 102: ...www baldormotion com 5 28 Input Output MN1943 ...
Page 136: ...www baldormotion com 7 8 Troubleshooting MN1943 ...
Page 172: ...www baldormotion com 8 36 Specifications MN1943 ...
Page 188: ...www baldormotion com B 6 Control System MN1943 ...
Page 204: ...www baldormotion com C 16 Mint Keyword Summary MN1943 ...
Page 216: ...Index MN1943 ...
Page 218: ...www baldormotion com Comments MN1943 Thank you for taking the time to help us ...
Page 219: ......
Page 220: ......