www.baldormotion.com
3-24 Basic Installation
MN1943
3.5.2 ‘Power ready’ input / output
A digital output on the source drive must be connected to a digital input on each of the receiving
drives (see Figure 12). This allows the source drive to inform the receiving drives when the DC
bus is ready for use. On each drive, the chosen output / input must also be configured as the power
ready output / input. Failure to connect and configure a ‘power ready’ signal will result in the
receiving drive reporting a ‘power base not ready’ error.
The configuration of the power ready output or input is performed in Mint WorkBench’s
Drive Setup
Wizard
, which appears as part of the Commissioning Wizard. This is explained in section 6.4.4.2.
The
POWERREADYOUTPUT
and
POWERREADYINPUT
keywords provide an alternative method for
assigning the power ready output and input. See the Mint help file for details.
The input and output must both be ‘active high’, and the input must also be level triggered (the
default settings).
DOUT1+
MotiFlex
e
100
DOUT1-
‘X3’
SOURCE
DRIVE
DIN1+
MotiFlex
e
100
DIN1-
18
6
‘X3’
15
3
Mint
POWERREADYOUTPUT
RECEIVING
DRIVE 1
Mint
POWERREADYINPUT
Customer
supplied
24VDC
supply
+24VDC
0V
DIN1+
MotiFlex
e
100
DIN1-
18
6
‘X3’
RECEIVING
DRIVE 2
DIN1+
MotiFlex
e
100
DIN1-
18
6
‘X3’
RECEIVING
DRIVE 3
Mint
POWERREADYINPUT
Mint
POWERREADYINPUT
Figure 12 - ‘Power ready’ output and input connections
Summary of Contents for MotiFlex e100
Page 1: ......
Page 2: ......
Page 60: ...www baldormotion com 3 44 Basic Installation MN1943 ...
Page 102: ...www baldormotion com 5 28 Input Output MN1943 ...
Page 136: ...www baldormotion com 7 8 Troubleshooting MN1943 ...
Page 172: ...www baldormotion com 8 36 Specifications MN1943 ...
Page 188: ...www baldormotion com B 6 Control System MN1943 ...
Page 204: ...www baldormotion com C 16 Mint Keyword Summary MN1943 ...
Page 216: ...Index MN1943 ...
Page 218: ...www baldormotion com Comments MN1943 Thank you for taking the time to help us ...
Page 219: ......
Page 220: ......