Media Server alarms
S8300 alarms – UPS
320
Maintenance of the Avaya G350 Media Gateway
June 2004
S8300 alarms – UPS
See
on page 320 through
on page 325 for a list of S8300
Alarms – UPS.
Table 180: Alarm #49
Number
49
Source
UPS
Event ID
1-8
Alarm Level
Major (SUP)
Alarm Text Description
upsEstimatedMinutesRemaining
Possible Causes
UPS does not have AC power source
Determining Cause
Alarm condition present indicates the problem occurred.
Resolution
Return AC power to UPS
Table 181: Alarm #50
Number
50
Source
UPS
Event ID
12
Alarm Level
Major
Alarm Text Description
upsAlarmShutdownPending
Possible Causes
A shutdown-after-delay countdown is underway -- i.e., the UPS
has been commanded off
Determining Cause
Alarm condition present indicates the problem occurred.
Resolution
Table 182: Alarm #51
Number
51
Source
UPS
Event ID
13
Alarm Level
Major
Alarm Text Description
upsAlarmShutdownImminent
Possible Causes
UPS will turn off power to the load in less than 5 seconds
Determining Cause
Alarm condition present indicates the problem occurred.
Resolution
Return AC power to UPS