Media Server alarms
S8300 alarms – _WD
314
Maintenance of the Avaya G350 Media Gateway
June 2004
Table 169: Alarm #14
Number
14
Source
_WD
Event ID
20
Alarm Level
Major
Alarm Text Description
Application totally failed
Possible Causes
Application failed maximum allowed number of times.
Determining Cause
Go to the Web Interface; choose Diagnostics; View System Logs;
select Watchdog Logs
Resolution
1. Access the web page; view summary status
2. If the application is down, use “start -s application” to start the
application.
3. From the Web Interface, choose Alarms and Notification; select
the appropriate alarm; choose Clear
Table 170: Alarm #15
Number
15
Source
_WD
Event ID
22
Alarm Level
Minor
Alarm Text Description
Application was shutdown
Possible Causes
Watchdog successfully shut down the named application
Determining Cause
Go to the Web Interface; choose Diagnostics; View System Logs;
select Watchdog Logs
Resolution
From the Web Interface, choose Alarms and Notification; select
the appropriate alarm; choose Clear
Table 171: Alarm #16 1 of 2
Number
16
Source
_WD
Event ID
23
Alarm Level
Major
Alarm Text Description
Watchd high monitor thread is rebooting the system
1 of 2