I2>1 Curve
IEC S Inverse 1
Editable Setting
By using the Plus / Up arrow key (+ /
) or the Minus / Down
arrow key (- /
) the desired
I2>1 Curve
can be set i.e. (Any of
the following Curve Selection IEC S Inverse 1 / IEC S Inverse 2
/ IEC V Inverse / IEC E Inverse / IEC LT Inverse / DT/ IEEE M
Inverse / IEEE V Inverse / IEEE E Inverse / IEEE Inverse /
IEEE ST Inverse and C12 User Defined).
Press the Left arrow key (
) to move to the next option.
tI2>1 DT Delay
001.00s
Editable Setting
By using the Plus / Up arrow key (+ /
) or the Minus / Down
arrow key (- /
) the desired
tI2>1 DT Delay
can be set
.
The setting range is from 000.00 to 100.00s in step of 0.01s.
Press the Left arrow key (
) to move to the next option.
I2>1 tRESET
DT
Read-only Setting
I2>1 tRESET
is fixed i.e. DT (Definite Time).
Press the Left arrow key (
) to move to the next option.
tI2>1tRESETDelay
001.00s
Editable Setting
By using the Plus / Up arrow key (+ /
) or the Minus / Down
arrow key (- /
) the desired
tI2>1tRESETDelay
can be set
.
The setting range is from 000.00 to 100.00s in step of 0.10s.
Press the Left arrow key (
) to move to the next option.
I2>1 2nd Hrm BLK
Disabled
Editable Setting
By using the Plus / Up arrow key (+ /
) or the Minus / Down
arrow key (- /
) the desired
I2>1 2nd Hrm BLK
function can
be set i.e. Disabled / Enabled.
Press the Left arrow key (
) to move to the next option.
I2>2 Enable
Yes
Editable Setting
By using the Plus / Up arrow key (+ /
) or the Minus / Down
arrow key (- /
) the desired
I2>2 Enable
function
can be set
Summary of Contents for ADR241B
Page 10: ...Page intentionally Left Blank...
Page 20: ...Page intentionally Left Blank...
Page 34: ...Page intentionally Left Blank...
Page 50: ...Page intentionally Left Blank...
Page 87: ...Page intentionally Left Blank...
Page 111: ...Page intentionally Left Blank...
Page 115: ...Page intentionally Left Blank...
Page 129: ...Page intentionally Left Blank...
Page 145: ...Page intentionally Left Blank...
Page 217: ...Page intentionally Left Blank...
Page 255: ...Page intentionally Left Blank...
Page 261: ...ADR241B Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM DR Rev No 06 Page No 261 of 272 Event Record...
Page 262: ...Page intentionally Left Blank...