ADR241B
Doc ID : ADR241B-DO_IM_01
Ref ID : ADR241B/IM/PLF
Rev No.
: 06
Page No. : 92 of 272
Table1. The Communication settings
Sr. No.
Setting Parameters
Setting ranges
1.
Unit ID
0001 - 0250
2.
Com Port
USB/ RS485
3.
Set RP Parity
None/Even/Odd
4.
Set RP Baud rate
9600/14400/19200/28800/38400/57600
The above settings are used to establish the proper communication between the IED (Rear
Port RS485) and Relay Talk V2 software from the Computer. The above settings should be
set the same in Relay Talk as well in the IED for the successful communication.
The USB port settings (USB Parity and Baud rate) are fixed i.e. Parity: None and Baud rate:
57600.
CT and Frequency Settings
The Current transformer setting is required to set for perfect scaling for current
measurement. The primary and secondary values of current settings are set in the IED and
system nominal frequency as given below table.
Table 2. The frequency and CT settings.
SL.NO
Setting Parameters
Setting ranges
1. Frequency
50Hz/60Hz
2. PH CT Secondary
1A/5A
3. PH CT Primary
10A to 5000 A
4. EF CT Secondary
1A/5A
5. EF CT Primary
10A to 5000 A
The above settings are have to be set based on the Electrical power system parameters to
establish the proper measurement of current in the IED.
Local Control Setting
A Local Control parameter setting is provided with Enable or Disable option. This is used to
operate the relay locally by issuing the CB Trip/ Close command through the relay HMI when
it is enabled.
DR Pre Trigger Setting
The Disturbance Recorder Pre Trigger setting is provided with setting range of 10 % to 90%.
This is used to set the pre fault delay in the Disturbance Recorder.
Summary of Contents for ADR241B
Page 10: ...Page intentionally Left Blank...
Page 20: ...Page intentionally Left Blank...
Page 34: ...Page intentionally Left Blank...
Page 50: ...Page intentionally Left Blank...
Page 87: ...Page intentionally Left Blank...
Page 111: ...Page intentionally Left Blank...
Page 115: ...Page intentionally Left Blank...
Page 129: ...Page intentionally Left Blank...
Page 145: ...Page intentionally Left Blank...
Page 217: ...Page intentionally Left Blank...
Page 255: ...Page intentionally Left Blank...
Page 261: ...ADR241B Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM DR Rev No 06 Page No 261 of 272 Event Record...
Page 262: ...Page intentionally Left Blank...