ADR241B
Doc ID : ADR241B-DO_IM_01
Ref ID : ADR241B/IM/I&P
Rev No.
: 06
Page No. : 44 of 272
2.3.8
Power Supply Connections
These should be wired with 1.5 mm PVC insulated multi-stranded copper wire terminated
with pin type lug. The wire should have a minimum voltage rating of 300 V RMS.
As per the application, in case auxiliary supply input of the relay needs to be wired, then
adequate care should be taken to wire as per polarity marking on the Terminal sticker at the
rear of the relay. The supply range is also mentioned on the Terminal sticker and before
energising, care should be taken to confirm that the auxiliary supply being wired is within
range.
2.3.9
Earth Connection
Every device must be connected to the cubicle earthing bar. Earthing terminal is provided on
back side of the relay. Ensure that the relay earthing is connected to the local earth bar. With
several relays present; make sure that the copper earth bar is properly installed for solidity
connecting to the earthing terminal of each relay equipment box.
Before energizing the equipment it must be earthed using the protective conductor terminal,
(if provided) or the appropriate termination of the supply plug in the case of plug connected
equipment. The protective conductor (earth) connection must not be removed since the
protection against electric shock provided by the equipment would be lost. The
recommended minimum protective conductor (earth) wire size is 2.5 mm² or as per industries
standard practice. The protective conductor (earth) connection must be of low-inductance
and as short as possible.
Note: To prevent any possibility of electrolytic action between brass or copper ground conductors
and the rear panel of the product, precautions should be taken to isolate them from one
another. This could be achieved in several ways, including placing a nickel-plated or
insulating washer between the conductor and the product case, or using tinned ring
terminals.
2.3.10
Current Transformers
Current transformers would generally be wired with 2.5 mm
2
PVC insulated multi-stranded
copper wire terminated with M4 ring terminals. The wires should be terminated with rings
using 90º rings terminals, with no more than two rings per terminal.
Due to the physical limitations of the ring terminal, the maximum wire size user can use is
4.0 mm
2
using ring terminals.
The wire should have a minimum voltage rating of 300 V RMS.
Caution: Current transformer circuits must never be fused.
Summary of Contents for ADR241B
Page 10: ...Page intentionally Left Blank...
Page 20: ...Page intentionally Left Blank...
Page 34: ...Page intentionally Left Blank...
Page 50: ...Page intentionally Left Blank...
Page 87: ...Page intentionally Left Blank...
Page 111: ...Page intentionally Left Blank...
Page 115: ...Page intentionally Left Blank...
Page 129: ...Page intentionally Left Blank...
Page 145: ...Page intentionally Left Blank...
Page 217: ...Page intentionally Left Blank...
Page 255: ...Page intentionally Left Blank...
Page 261: ...ADR241B Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM DR Rev No 06 Page No 261 of 272 Event Record...
Page 262: ...Page intentionally Left Blank...