Doc ID : ADR241B-DO_IM_01
Ref ID : ADR241B/IM/TC
Rev No.
: 06
Page No. : 269 of 272
ADR241B
6. Set and apply 2 times current value and measure the timing on timer.
7. The measured timing should be ±5% of actual timing (10.029 Sec).
8. Repeat the above procedure for remaining phases and Earth Fault.
Phase Protection Test: -
Setting IP>1: ________ IP>1 TMS =: _______
Threshold
Theoretical Value
Relay Value
IP>1 Threshold
________A
________A
IP>1 Drop Threshold
________A
________A
Time Delay Setting = _________
IDMT Characteristics = ________ 10 Times _________Sec. (take value from selected curve)
Threshold
Relay
Time Delay at 2 times of IP>1 setting
________ms
________ms
Time Delay at 10 times of IP>1 setting
________ms
________ms
Earth Protection Test: -
Setting IE>1: ________ IE>1 TMS = :_______
Threshold
Theoretical Value
Relay Value
IE>1 Threshold
________A
________A
IE>1 Drop Threshold
________A
________A
Time Delay Setting = _________
IDMT Characteristics = __________ 10 Times _________Sec.
Threshold
Relay
Time Delay at 2 times of IE>1 setting
________ms
________ms
Time Delay at 10 times of IE>1 setting
________ms
________ms
Testing of Binary Input:
1. The Binary inputs can be tested by applying 24-230V DC voltage to respective binary input
terminals.
2. Observed binary input status in STATUS menu on LCD display
3. Following are the binary inputs terminals
Binary Input Terminals
Binary Input
B1 – B2
Opto I/P-In1
B1 – B3
Opto I/P-In2
B1 – B4
Opto I/P-In3
B1 – B5
Opto I/P-In4
Summary of Contents for ADR241B
Page 10: ...Page intentionally Left Blank...
Page 20: ...Page intentionally Left Blank...
Page 34: ...Page intentionally Left Blank...
Page 50: ...Page intentionally Left Blank...
Page 87: ...Page intentionally Left Blank...
Page 111: ...Page intentionally Left Blank...
Page 115: ...Page intentionally Left Blank...
Page 129: ...Page intentionally Left Blank...
Page 145: ...Page intentionally Left Blank...
Page 217: ...Page intentionally Left Blank...
Page 255: ...Page intentionally Left Blank...
Page 261: ...ADR241B Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM DR Rev No 06 Page No 261 of 272 Event Record...
Page 262: ...Page intentionally Left Blank...