ADR241B
Doc ID : ADR241B-DO_IM_01
Ref ID : ADR241B/IM/SS
Rev No.
: 06
Page No. : 118 of 272
6
SETTING SHEET
6.1
General Settings
Sr. No
Parameter
Defaults setting
Setting / Ranges
1.
Password
0000
0000 to 9999
This setting specifies to enter the set password
2.
New Password
0000
0000 to 9999
This setting specifies to set the new password
3.
Unit ID
001
000 to 250 in step of 1
This cell sets the unique address for the relay such that only one relay is accessed by master station
software.
4.
Com Port
USB
USB/RS485
This setting specifies to select communication port for 103 communications.
5.
Set RP Parity
None
None/Even/Odd
This cell controls the Rear Port parity format used in the data frames. It is important that both relay and
master station are set with the same parity setting.
6.
Set RP Baud Rate
57600
9600/14400/19200/28800/38400/57600
This cell controls the communication speed between relay and master station. It is important that both
relay and master station are set at the same speed setting.
7.
Frequency
50Hz
50Hz/60Hz
This setting determines to select the system frequency
8.
Ph CT Secondary
1 A
1 A/5 A
This setting is used to set the Ph CT Secondary
9.
Ph CT Primary
10 A
10 to 5000 A in step of 10A
This setting is used to set the Ph CT Primary.
10.
EF CT Secondary
1 A
1 A/5 A
This setting is used to set the EF CT Secondary
11.
EF CT Primary
10 A
10 to 5000 A in step of 10A
This setting is used to set the EF CT Primary.
12.
TCS Enable
No
Yes/No
This setting is used to enable (turn on) or disable (turn off) Trip circuit supervision. This is used to
monitor trip coil which is used to trip the circuit breaker.
13.
TCS Delay
0.50
0.00 to 1.00 sec in step of 0.10 sec
This setting is used to set the time-delay for the Trip Circuit supervision.
14.
50 BF
Byp
Byp/Int/Ext
This setting is used to enable (turn on) or disable (turn off) Internal Breaker Failure initiation or External
Breaker Failure Initiation and also can bypass this function.
15.
50 BF Delay
0.50
0.00 to 600 sec in step of 0.10 sec
This setting for the time-delay for the CBF trip.
16.
50 BF_I
100%
5% to 100% in step of 1%
This setting is used to set the current threshold value above which the breaker failure will operate after
the set time delay is expired.
Summary of Contents for ADR241B
Page 10: ...Page intentionally Left Blank...
Page 20: ...Page intentionally Left Blank...
Page 34: ...Page intentionally Left Blank...
Page 50: ...Page intentionally Left Blank...
Page 87: ...Page intentionally Left Blank...
Page 111: ...Page intentionally Left Blank...
Page 115: ...Page intentionally Left Blank...
Page 129: ...Page intentionally Left Blank...
Page 145: ...Page intentionally Left Blank...
Page 217: ...Page intentionally Left Blank...
Page 255: ...Page intentionally Left Blank...
Page 261: ...ADR241B Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM DR Rev No 06 Page No 261 of 272 Event Record...
Page 262: ...Page intentionally Left Blank...