ADR241B
Doc ID : ADR241B-DO_IM_01
Ref ID : ADR241B/IM/SS
Rev No.
: 06
Page No. : 126 of 272
6.10
Inrush Blocking
Sr. No
Parameter
Settings / Ranges
1.
Password
0000
0000 to 9999
This setting specifies to enter the set password
2.
2nd Hrm BLK
Disabled
Enabled/Disabled
To enable (turn on) or disable (turn off) the 2nd Harmonic blocking of the over current/earth fault
3.
2nd Hrm Threshold
20%
5 to 70 % in step of 1%
This setting is specify the 2
nd
Harm Threshold value, if the level of 2nd harmonic/fundamental in any
phase current or neutral current exceeds the setting, the over current protection will be blocked as
selected
4.
I> UB2H
1000%
200 to 3000 % in step of 1%
The 2nd harmonic blocking applied only when the fundamental current is above 2nd Harm Thresh and
below I> UB2H setting. The reset levels are 95% of these thresholds
6.11
Date and Time setting
Sr. No
Parameter
Defaults setting
Settings / Ranges
1.
SET Hours
00
00 to 23 Hrs in step 1.
Hour
setting
needed when relay is not connected to SCADA system
2.
SET Minutes
00
00 to 59 Mins in step 1.
Minutes
setting
needed when relay is not connected to SCADA system
3.
SET Seconds
00
00 to 59Sec. in step 1.
Seconds
setting
needed when relay is not connected to SCADA system
4.
SET Date
01
01 to 31 Days in step of 1.
Date
needed when relay is not connected to SCADA system
5.
SET Month
01
01 to 12 Months in step of 1.
Month
needed when relay is not connected to SCADA system
6.
SET Year
01
00 to 99 Years in step of 1.
Year
needed when relay is not connected to SCADA system
6.12
Reclosing
Sr. No
Parameter
Defaults setting
Setting / Ranges
1.
Password
0000
0000 to 9999
This setting specifies to enter the set password
2.
Reclosing
0000
0 to 4 in step of 1 (0 for Disable)
This setting is used to disable or set the No of reclosing shots.
3.
Dead Time 1
0.1s
0.10 to 180.00s in step of 0.10s
This setting is used to set the dead time 1
4.
Dead Time 2
0.1s
0.10 to 180.00s in step of 0.10s
This setting is used to set the dead time 2
5.
Dead Time 3
0.1s
0.10 to 180.00s in step of 0.10s
Summary of Contents for ADR241B
Page 10: ...Page intentionally Left Blank...
Page 20: ...Page intentionally Left Blank...
Page 34: ...Page intentionally Left Blank...
Page 50: ...Page intentionally Left Blank...
Page 87: ...Page intentionally Left Blank...
Page 111: ...Page intentionally Left Blank...
Page 115: ...Page intentionally Left Blank...
Page 129: ...Page intentionally Left Blank...
Page 145: ...Page intentionally Left Blank...
Page 217: ...Page intentionally Left Blank...
Page 255: ...Page intentionally Left Blank...
Page 261: ...ADR241B Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM DR Rev No 06 Page No 261 of 272 Event Record...
Page 262: ...Page intentionally Left Blank...