ADR241B
Doc ID : ADR241B-DO_IM_01
Ref ID : ADR241B/IM/I&P
Rev No.
: 06
Page No. : 43 of 272
Auxiliary power/ Input/ Output Connections
The terminal block of ADR241B used for Auxiliary supply, Status input, relay output contacts
& Rear communication port is as shown below. The wires should be terminated with straight
pin type lugs, with no more one lug per terminal.
The terminal blocks used for ADR241B relay is as shown below.
Figure
7
: Terminal blocks for Auxiliary/ Input/ Output
Caution: Always fit an insulating sleeve over the pin type lug.
Rear Serial Port connection
The rear serial port is intended for use with a permanently wired connection to a remote
SCADA system. The physical connectivity is achieved using this terminal for signal
connection. The terminal block is located at the rear of the relay as shown below.
Figure
8
: Rear Serial port terminal block
For connecting the RS485, use screened cable with a maximum total length of 1000 m or
200 nF total cable capacitance.
A typical cable specification would be:
Each core: 16/0.2 mm
2
copper conductors, PVC insulated
Nominal conductor area: 0.5 mm
2
per core
Screen: Overall braid, PVC sheathed
There is no electrical connection of the cable screen to the device. The link is provided
purely to link together the two cable screens.
Summary of Contents for ADR241B
Page 10: ...Page intentionally Left Blank...
Page 20: ...Page intentionally Left Blank...
Page 34: ...Page intentionally Left Blank...
Page 50: ...Page intentionally Left Blank...
Page 87: ...Page intentionally Left Blank...
Page 111: ...Page intentionally Left Blank...
Page 115: ...Page intentionally Left Blank...
Page 129: ...Page intentionally Left Blank...
Page 145: ...Page intentionally Left Blank...
Page 217: ...Page intentionally Left Blank...
Page 255: ...Page intentionally Left Blank...
Page 261: ...ADR241B Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM DR Rev No 06 Page No 261 of 272 Event Record...
Page 262: ...Page intentionally Left Blank...