Definite time Over current (C6)
•
IEEE Moderately Inverse Curve (C7)
•
IEEE Very Inverse Curve (C8)
•
IEEE Extremely Inverse Curve (C9)
•
IEEE Inverse Curve (C10)
•
IEEE Short Time Inverse Curve (C11)
•
User Define Curve (C12)
The over current, earth fault and negative sequence O/C function are programmable as per
IDMT characteristic based on IEC and IEEE/ANSI standards. The inverse time delay is
calculated with the following mathematical formula:
Where
t
: Operation time
K : Constant (see the table)
I
: Measured current
I
s
: Current threshold setting (also refer as Gs as IEC standard notation)
α : Constant (see the table)
L : ANSI/IEEE constant (zero for IEC curve)
T : Time multiplier setting (TMS) for IEC & IEEE curves
Description
Standard
K
α
L
IEC Standard Inverse 1
IEC
0.14
0.02
0
IEC Standard Inverse 2
IEC
0.06
0.02
0
IEC Very Inverse
IEC
13.5
1
0
IEC Extremely Inverse
IEC
80
2
0
IEC Long Time Inverse
IEC
120
1
0
Definite Time
-
-
-
-
IEEE Moderately Inverse
IEEE
0.0515
0.02
0.114
IEEE Very Inverse
IEEE
19.61
2
0.491
IEEE Extremely Inverse
IEEE
28.2
2
0.1217
IEEE Inverse
IEEE
5.95
2
0.18
IEEE Short Time Inverse
IEEE
0.0239
0.02
0.0169
User Define Curve
-
-
-
-
t = T*
K
I
Is
α
– 1
+ L
Summary of Contents for ADR241B
Page 10: ...Page intentionally Left Blank...
Page 20: ...Page intentionally Left Blank...
Page 34: ...Page intentionally Left Blank...
Page 50: ...Page intentionally Left Blank...
Page 87: ...Page intentionally Left Blank...
Page 111: ...Page intentionally Left Blank...
Page 115: ...Page intentionally Left Blank...
Page 129: ...Page intentionally Left Blank...
Page 145: ...Page intentionally Left Blank...
Page 217: ...Page intentionally Left Blank...
Page 255: ...Page intentionally Left Blank...
Page 261: ...ADR241B Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM DR Rev No 06 Page No 261 of 272 Event Record...
Page 262: ...Page intentionally Left Blank...