ADR241B
Doc ID : ADR241B-DO_IM_01
Ref ID : ADR241B/IM/SS
Rev No.
: 06
Page No. : 122 of 272
6.5
Negative Sequence Over current
Sr. No
Parameter
Defaults setting
Setting / Ranges
1.
Password
0000
0000 to 9999
This setting specifies to enter the set password
2.
I2>1 Enable
Yes
Yes/No
This setting determine to enable (turn on) or disable (turn off) the Negative Sequence Over Current
function stage 1
3.
I2>1
100%
1% to 250% in step of 1%
This setting determines Pick-up setting for first stage negative sequence over current element.
4.
I2>1 TMS
1.00
0.01 to 10.0 in step of 0.005
This setting for the time multiplier setting to adjust the operating time of the IDMT characteristic.
5.
I2>1 Curve
IEC S Inverse 1
IEC S Inverse 1 / IEC S Inverse 2 /
IEC V Inverse / IEC E Inverse / IEC
LT Inverse / DT / IEEE M Inverse /
IEEE V Inverse / IEEE E Inverse /
IEEE Inverse / IEEE ST Inverse /
C12 User Defined
This setting is used to select the IDMT curves for the various applications.
6.
tI2>1 DT Delay
0 s
0 to 100.0 in step of 0.01s
This setting is used to set the time-delay for the Definite Time (DT) setting if selected for first stage
negative sequence over current element.
7.
I2>1 tRESET
DT
Not Editable
This setting determines the DT (Fix) reset/release characteristic.
8.
tI2>1 tRESET Delay
1.00 s
0.00 to 100s in steps of 0.10s
This setting determines the reset/release time for Definite Time (DT).
9.
I2>1 2nd Hrm BLK
Disable
Enable/ Disable
This setting determines the enable (turn on) or disable (turn off) the first stage negative sequence
over current element to block the trip command in presence of inrush current.
10.
I2>2 Enable
Enable
Enable/ Disable
This setting determine to enable (turn on) or disable (turn off) the Negative sequence over current
function stage 2
11.
I2>2
100%
5% to 3000% in step of 1%
This setting determines Pick-up setting for second stage negative sequence over current element.
12.
tI2>2 Delay
1.00 Sec
00.0 to 100 sec in step of 0.01Sec
This setting for the time-delay for the definite time setting if selected for second stage negative
sequence over current element.
13.
I2>2 2nd Hrm BLK
Disable
Enable/ Disable
This setting determines the enable (turn on) or disable (turn off) the second stage negative
sequence over current element to block the trip command in presence of inrush current.
Summary of Contents for ADR241B
Page 10: ...Page intentionally Left Blank...
Page 20: ...Page intentionally Left Blank...
Page 34: ...Page intentionally Left Blank...
Page 50: ...Page intentionally Left Blank...
Page 87: ...Page intentionally Left Blank...
Page 111: ...Page intentionally Left Blank...
Page 115: ...Page intentionally Left Blank...
Page 129: ...Page intentionally Left Blank...
Page 145: ...Page intentionally Left Blank...
Page 217: ...Page intentionally Left Blank...
Page 255: ...Page intentionally Left Blank...
Page 261: ...ADR241B Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM DR Rev No 06 Page No 261 of 272 Event Record...
Page 262: ...Page intentionally Left Blank...