6.6
Cold Load
Sr. No
Parameter
Defaults setting
Setting / Ranges
1.
Password
0000
0000 to 9999
This setting specifies to enter the set password
2.
Cold load Enable
No
Yes/No
This setting determine to enable (turn on) or disable (turn off) the Cold load function.
3.
t_CLP Timer
1.00 Sec
0.00 to 100.0s in step of 0.10s
This setting controls the period of time for which the relevant over current and ground over current
settings are altered or inhibited following circuit breaker closure.
4.
ICLP>1 Enable
Yes
Yes/No
This setting determine to enable (turn on) or disable (turn off) the Over Current function stage 1
5.
ICLP>1
100%
2% to 400% in step of 1%
This setting determines Pick-up setting for first stage over current element.
6.
ICLP>1TMS
1.00
0.01 to 10.0 in step of 0.005
This setting for the time multiplier setting to adjust the operating time of the IDMT characteristic.
7.
ICLP>1Curve
IEC S Inverse 1
IEC S Inverse 1 / IEC S Inverse 2 / IEC V
Inverse / IEC E Inverse / IEC LT Inverse /
DT / IEEE M Inverse / IEEE V Inverse /
IEEE E Inverse / IEEE Inverse / IEEE ST
Inverse / C12 User Defined
This setting determines the tripping characteristic for the first stage over current element.
8.
tICLP>1 DT Delay
1.00 Sec
0.00 to 100.0s in step of 0.01s
This setting is used to set the time-delay for the Definite Time (DT) setting if selected for first stage over
current element.
9.
ICLP>2 Enable
Yes
Yes/No
This setting determine to enable (turn on) or disable (turn off) the Over Current function stage 2
10.
ICLP>2
100%
5 to 4000 % in step of 1%
This setting determines Pick-up setting for second stage over current element.
11.
tICLP>2 Delay
0.10 Sec
00.0 to 100 sec in step of 0.01Sec
This setting for the time-delay for the definite time setting if selected for second stage over current
element.
12.
IECLP>1 Enable
Yes
Yes/No
This setting determine to enable (turn on) or disable (turn off) the Ground over current function stage 1
13.
IECLP>1
100%
1% to 400% in step of 1%
This setting determines Pick-up setting for first stage Ground over current (Measured) element.
14.
IECLP>1TMS
1.00
0.01 to 10.0 in step of 0.005
This setting for the time multiplier setting to adjust the operating time of the IDMT characteristic.
15.
IECLP>1Curve
IEC S Inverse 1
IEC S Inverse 1 / IEC S Inverse 2 / IEC V
Inverse / IEC E Inverse / IEC LT Inverse /
DT / IEEE M Inverse / IEEE V Inverse /
IEEE E Inverse / IEEE Inverse / IEEE ST
Inverse / C12 User Defined
This setting determines the tripping characteristic for the first stage Ground over current (Measured)
element.
Summary of Contents for ADR241B
Page 10: ...Page intentionally Left Blank...
Page 20: ...Page intentionally Left Blank...
Page 34: ...Page intentionally Left Blank...
Page 50: ...Page intentionally Left Blank...
Page 87: ...Page intentionally Left Blank...
Page 111: ...Page intentionally Left Blank...
Page 115: ...Page intentionally Left Blank...
Page 129: ...Page intentionally Left Blank...
Page 145: ...Page intentionally Left Blank...
Page 217: ...Page intentionally Left Blank...
Page 255: ...Page intentionally Left Blank...
Page 261: ...ADR241B Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM DR Rev No 06 Page No 261 of 272 Event Record...
Page 262: ...Page intentionally Left Blank...