Release Note

Guardmaster MSR57P Speed Monitoring 
Safety Relay

Catalog Number 440R-S845AER-NNL

About This Publication

This document explains how to install new firmware into the MSR57P 
safety relay. These release notes correspond to revision 1.005 of the 
MSR57P firmware.

Before You Begin

The procedure assumes that you have Drive Explorer software, 
version 5.02.07 or later, installed on your PC and you have 
successfully connected to the MSR57P relay.

Topic

Page

About This Publication

1

Before You Begin

1

Corrected Anomalies

3

Update Firmware

3

Confirm the Update

6

Download Your Saved Configuration File

6

Additional Resources

7

TIP

If you do not have DriveExplorer software, you can 
download the free version, DriveExplorer Lite, at 

www.ab.com/drives/driveexplorer/free_download.html.

Power Status 
Indicator

Type A to Type B USB 
Cable

1202-C10 Cable

1203-SFC Cable

Power Status 
Indicator

Using USB Converter

Using Serial Converter

20-HIM-H10 Cable

DriveExplorer Software

DriveExplorer Software

Summary of Contents for 440R-S845AER-NNL

Page 1: ...d you have successfully connected to the MSR57P relay Topic Page About This Publication 1 Before You Begin 1 Corrected Anomalies 3 Update Firmware 3 Confirm the Update 6 Download Your Saved Configuration File 6 Additional Resources 7 TIP If you do not have DriveExplorer software you can download the free version DriveExplorer Lite at www ab com drives driveexplorer free_download html Power Status ...

Page 2: ...ecurity group 4 Place the relay in Run mode by setting the P6 Operating Mode parameter to 1 5 Record the value of the P10 Signature ID parameter You will need to verify this value is unchanged after you reload your configuration following the update 6 From the Actions menu choose Upload and Save to save your configuration 7 Browse to the directory where you want to save your file 8 Name the file a...

Page 3: ...red as 2NC 3s and only one of the channels turned OFF opened the relay would detect the fault and perform the required stop function You should be required to open both channels on that input for a successful reset command Corrected firmware requires that both input channels be cycled to OFF open before a reset into actively monitoring motion is permitted Dual Feedback Speed fault occurs when safe...

Page 4: ...7P Speed Monitoring Safety Relay 3 Select the MSR57P relay and click the information icon to open the relay Properties dialog box 4 Select the Details tab to view the revision levels currently installed on your MSR57P relay 5 Click Flash Update 6 Click Browse ...

Page 5: ...ctory 8 Select 1 005 and click Next 9 On the Confirm Flash Update dialog box click FLASH to start the update It takes approximately 7 10 minutes to update the relay The Executing Flash Update dialog box tracks the progress of the update 10 When the update is complete click Close 11 Click Yes when Drive Explorer software requests to reconnect to the MSR57P relay ...

Page 6: ...may change 4 Browse to the configuration file you saved before performing the firmware update csf file 5 Select your file and click Open 6 Expand the Parameters and choose the Security group 7 Compare the value of P10 Signature ID to the value you recorded before the upgrade The two values should be the same 8 Place the relay in Run mode by setting the P6 Operating Mode parameter to 1 File Revisio...

Page 7: ...perating an MSR57P relay including safety requirements refer to the Guardmaster MSR57P Speed Monitoring Safety Relay User Manual publication 440R UM004A EN P You can view or download publications at http literature rockwellautomation com To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative ...

Page 8: ...ew the information that s contained in this manual You can also contact a special Customer Support number for initial help in getting your product up and running New Product Satisfaction Return Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follo...

Reviews: