Doc ID : ADR241B-DO_IM_01
Ref ID : ADR241B/IM/TC
Rev No.
: 06
Page No. : 268 of 272
ADR241B
Step1.
Connect all terminals as per the chart.
Step2.
Adjust rated CT Secondary Current 1A/5A. Observe the current value from
measurement menu. The actual current should match with relay display.
Step3.
Repeat the same procedure for other element.
Current Measurement
Applied Value
Measured value
11.5
Pick up and Trip Test:
1. Connect current source at A phase CT terminals 1A/5A current input terminal.
2. Set current setting value to 100% i.e. 1A/5A, TMS at Minimum (x0.01) value.
3. Start current injector to & increase current value till relay get pick up and trip. The
operating value should be within 1 to 1.1 times of set pickup value.
4. Select the Curve IEC S Inverse 1 and Set the TMS at 1.00.
5. Connect the assigned trip contact to Timer.