ADR241B
Doc ID : ADR241B-DO_IM_01
Ref ID : ADR241B/IM/SS
Rev No.
: 06
Page No. : 124 of 272
16.
tIECLP>1DT Delay
1.00 Sec
0.00 to 100.0s in step of 0.01s
This setting is used to set the time-delay for the Definite Time (DT) setting if selected for first stage
Ground over current (Measured) element.
17.
IECLP>2 Enable
Yes
Yes/No
This setting determine to enable (turn on) or disable (turn off) the Ground over current (Measured)
function stage 2
18.
IECLP>2
100%
5 to 3000 % in step of 1%
This setting determines Pick-up setting for second stage Ground over current (Measured) element.
19.
tIECLP>2 Delay
0.10 Sec
00.0 to 100 sec in step of 0.01Sec
This setting for the time-delay for the definite time setting if selected for second stage Ground over
current (Measured) element.
20.
3IoCLP>1 Enable
Yes
Yes/No
This setting determine to enable (turn on) or disable (turn off) the residual over current (3Io)function
stage 1
21.
3IoCLP>1
100%
2% to 250% in step of 1%
This setting determines Pick-up setting for first stage Residual over current (3Io) element.
22.
3IoCLP>1TMS
1.00
0.01 to 10.0 in step of 0.005
This setting for the time multiplier setting to adjust the operating time of the IDMT characteristic.
23.
3IoCLP>1Curve
IEC S Inverse 1
IEC S Inverse 1 / IEC S Inverse 2 / IEC V
Inverse / IEC E Inverse / IEC LT Inverse /
DT / IEEE M Inverse / IEEE V Inverse /
IEEE E Inverse / IEEE Inverse / IEEE ST
Inverse / C12 User Defined
This setting determines the tripping characteristic for the first stage Residual over current (3Io) element.
24.
t3IoCLP>1DT Delay
1.00 Sec
0.00 to 100.0s in step of 0.01s
This setting is used to set the time-delay for the Definite Time (DT) setting if selected for first stage
Residual over current (3Io) element.
25.
3IoCLP>2 Enable
Yes
Yes/No
This setting determine to enable (turn on) or disable (turn off) the Residual over current (3Io)function
stage 2
26.
3IoCLP>2
100%
5 to 3000 % in step of 1%
This setting determines Pick-up setting for second stage Residual over current (3Io) element.
27.
t3IoCLP>2 Delay
0.10 Sec
00.0 to 100 sec in step of 0.01Sec
This setting for the time-delay for the definite time setting if selected for second stage Residual over
current (3Io) element.
6.7
I2/I1> (46BC)
Sr. No
Parameter
Defaults setting
Setting / Ranges
1.
Password
0000
0000 to 9999
This setting specifies to enter the set password
2.
I2/I1>1 Enable
No
Yes/ No
This setting is used to disable or enable the first stage of broken conductor function.
3.
I2/I1>1
20%
5% to 100% in step of 1%
Summary of Contents for ADR241B
Page 10: ...Page intentionally Left Blank...
Page 20: ...Page intentionally Left Blank...
Page 34: ...Page intentionally Left Blank...
Page 50: ...Page intentionally Left Blank...
Page 87: ...Page intentionally Left Blank...
Page 111: ...Page intentionally Left Blank...
Page 115: ...Page intentionally Left Blank...
Page 129: ...Page intentionally Left Blank...
Page 145: ...Page intentionally Left Blank...
Page 217: ...Page intentionally Left Blank...
Page 255: ...Page intentionally Left Blank...
Page 261: ...ADR241B Doc ID ADR241B DO_IM_01 Ref ID ADR241B IM DR Rev No 06 Page No 261 of 272 Event Record...
Page 262: ...Page intentionally Left Blank...