Rockwell Automation Publication 2198-UM004A-EN-P - October 2019
449
Upgrade the Drive Firmware
Appendix B
Inhibit Configure Logix 5000 Controller Communication
If the drive is configured as IO mode, you must inhibit the connection before
performing the firmware upgrade.
Follow these steps to inhibit the connection.
1.
Open your Logix Designer application.
2.
Right-click the 2198-Exxxx-ERS
drive and choose Properties.
The Module Properties dialog box
appears.
3.
Click the Connection tab.
4.
Check Inhibit Module.
5.
Click OK.
6.
Save your file and download the program to the controller.