Motion Control in PR Mode
Chapter 11
• If you write1…99 to PR command trigger register, the servo drive will
execute the specified PR command (1…99).
• If you write 1000, the servo drive will stop executing PR commands. which
is the same function as DI.STP [0x46] motor stop. Values 100…999 are
not valid.
When reading ID300 (P5.007) PRCmdTrigger, if the command is incomplete,
the drive reads the current command (1…99).
If the command is complete, the drive reads the current c10000. If the
command is complete, DO.TPOS [0x05] target position reached is on, and
motor position is reached, the drive reads the current c20000.
For example:If the value read is 3, it means PR#3 is incomplete. If the value read
is 10003, it means PR#3 completed, but the motor has not reached the target
position yet. If the value read is 20003, it means PR#3 completed and the motor
reached the target position.
Special Trigger (Capture, Compare, E-Cam)
You can use high-speed position capturing (Capture), high-speed position
comparing (Compare), and E-Cam function to trigger the specified PR
command. While the capturing completes, you can set Bit3 of ID331 (P5.039).X
or ID395 (P5.110).X to determine whether to trigger PR#50, or set Bit 0 of
ID351 (P5.059).U to determine whether to trigger PR#45 once the last data is
compared. If E-Cam disengagement setting is 2, 4, or 6, use ID376 (P5.088).BA
to write the PR command number.
High-speed Position Capture Function (CAP) on page 315
,
High-speed Position Compare Function (CMP) on page 322
, and
for more information.
For parameter descriptions and data, see the Knowledgebase article
Kinetix 5100 Servo Drive Parameter Data and Fault Codes.
The total number of Capture, Compare, or E-Cam cannot exceed 800 (the limit
of the data array). See
for more information about these applications.
Triggering method
Setting bit
Default Trigger PR Command
ID331 (P5.039) DI9CaptureControl
ID331 (P5.039).X Bit 3
PR#50
ID395 (P5.110) DI10CaptureControl
ID395 (P5.110).X Bit 3
PR#50
ID351 (P5.059) CompareControl
ID351 (P5.059).U Bit 0
PR#45
ID376 (P5.088) ECamControl
ID376 (P5.088).BA
User-defined