Chapter 10
Modes of Operation
Low Pass Filter for Torque Command
Scaling of Analog Command (Torque Mode)
The motor torque command is controlled by the analog voltage difference
between the T_REF and GND analog signals. The torque slope and its range can
be adjusted by the Analog to Torque Scale parameter.
Motor torque command is based on the following equation:
If the ID148 (P1.041) parameter is set at its default setting of 100 and the
external analog input voltage is 10V, the torque command is 100% of the rated
torque.
If the ID148 (P1.041) parameter is set to 300 and the external analog input
voltage is 10V, the torque command is 300% of the rated torque.
If the ID148 (P1.041) parameter is set at its default setting of 100 and the
external analog input voltage is 5V, the torque command is 50% of the rated
torque.
Table 85 - Relevant Parameter
Parameter
Name
ID123 (P1.007)
TorqueCmdLowPassFilterTime
Table 86 - Relevant Parameter
Parameter
Name
ID148 (P1.041)
AnalogToTorqueScale
Torque control command =
= Unit %
External analog input voltage x ID148 (P1.041) setting value
10
Torque control command =
= 100%
10V x 100
10
Torque control command =
= 300%
10V x 300
10
Torque control command =
= 50%
5V x 100
10