Rockwell Automation Publication 2198-UM004A-EN-P - October 2019
29
Plan and Install the Kinetix 5100 Drive System
Chapter 2
Figure 11 - Minimum Clearance Requirements
Table 11 - Dimension D
See Kinetix Servo Drives Specifications Technical Data, publication
for Kinetix 5100 drive dimensions.
ATTENTION:
To avoid damage to drives due to overheating, cooling fans must
be installed when 2198-E1004-ERS drives are mounted in the cabinet. Make
sure that there is a minimum of 0.5 m/s (1.6 ft/s) air flow at 10 mm (0.4 in.)
above the top-center of the drive.
20
(0.8)
Cabinet
50
(2.0)
D
80 (3.2)
Airflow
100
(4.0)
20
(0.8)
Airflow
20
(0.8)
20
(0.8)
D
D
50 (2.0)
Air Flow
Air Flow
Dimension D is determined
in
.
Measure
Airflow Here
Cooling Fans
10
(0.4)
Dimensions are in mm (in.)
Kinetix 5100 Drive
Cat. No.
Cooling Method
Temperature, Ambient Versus Dimension D
2198-E1004-ERS
Natural
2198-E1007-ERS
2198-E1015-ERS
2198-E1020-ERS
2198-E2030-ERS
2198-E2055-ERS
2198-E2075-ERS
2198-E2150-ERS
Forced Air
IMPORTANT
Mount the drive in an upright position as shown. Do not mount the drive on its
side.
77
82
97
102
112
122
25
30
35
40
45
50
0
5
10
15
20
Ta
°F
Ta
°C
D mm (in.)
(0.0)
(0.2)
(0.4)
(0.6)
(0.8)