Rockwell Automation Publication 2198-UM004A-EN-P - October 2019
21
Chapter
2
Plan and Install the Kinetix 5100 Drive System
This chapter describes system installation guidelines used in preparation for
mounting your Kinetix® 5100 drive components.
System Design Guidelines
Use the information in this section when you design your enclosure and plan to
mount your system components on the panel.
For online product selection and system configuration tools, including
AutoCAD (DXF) drawings of the product, see
http://www.rockwellautomation.com/global/support/selection.page
.
System Mounting Requirements
• To comply with UL and CE requirements, the Kinetix 5100 drive system
must be mounted in a grounded conductive enclosure offering protection
as defined in standard IEC 60529 to IP20 such that they are not accessible
to an operator or unskilled person.
• To maintain the functional safety rating of the Kinetix 5100 drive system,
this enclosure must be appropriate for the environmental conditions of the
industrial location and provide a protection class of IP54 or higher.
• The panel you install inside the enclosure for mounting your system
components must be on a flat, rigid, vertical surface that won’t be subjected
to shock, vibration, moisture, oil mist, dust, or corrosive vapors in
accordance with pollution degree 2 (EN 61800-5-1) because the product
is rated to protection class IP20 (EN 60529).
Topic
Page
ATTENTION:
Plan the installation of your system so that you can cut, drill, tap,
and weld with the system removed from the enclosure. Because the system is
of the open type construction, be careful to keep any metal debris from falling
into it. Metal debris or other foreign matter can become lodged in the circuitry,
which can result in damage to components.