Rockwell Automation Publication 1440-UM001D-EN-P - September 2016
97
Configure the XM-124 Standard Dynamic Measurement Module
Chapter 2
DeviceNet Network
The DeviceNet section shows the current setting of a connected modules
DeviceNet address and communication rate. If no module is connected, these
values display ‘Node address: 63’ and ‘Communication rate: AutoBaud’.
SW1 (leftmost switch): DIP switch enable/disable
SW2: Normal/Legacy mode selection
SW3 – SW4: Set the communication rate
SW5 – SW10: Set the MAC ID (DeviceNet address).
See
Set the Module DIP Switch on page 54
for details on how to set a node
address with DIP switches.
Firmware Update
The firmware update section shows the current firmware revision of the
connected module. The field is blank if no module is connected. To load new
firmware into the module, click update firmware.
View Data
The Data parameters are used to view the measured values of the input
channels and the 4…20 mA outputs, as well as to monitor the status of the
channels, alarms, and relays.
IMPORTANT
Before updating the firmware, be sure that the module is not slaved to an
XM-440 Master Relay module or to a scanner.
TIP
To view all data parameters in the XM Serial Configuration Utility, click
the View Data tab.
Communication
Rate
SW 3
SW 4
125 Kbps
0
0
250 Kbps
0
1
500 Kbps
1
0
Autobaud
1
1