Rockwell Automation Publication 1440-UM001D-EN-P - September 2016
Chapter 1
Install the XM-124 Standard Dynamic Measurement Module
XM Installation
Requirements
This section describes wire, power, grounding, and terminating resistor
requirements for an XMsystem.
Wiring Requirements
Use solid or stranded wire. All wiring must meet these specifications:
• 2.1…0.3 mm
2
(14…22 AWG) copper conductors without pretreatment;
8.4 mm
2
(8 AWG) required for grounding the DIN rail for
electromagnetic interference (EMI) purposes
• Recommended strip length 8 mm (0.31 in.)
• Minimum insulation rating of 300V
• Soldering the conductor is forbidden
• Wire ferrules can be used with stranded conductors; copper ferrules
recommended
ATTENTION:
The installation requirements can be different for different
XM modules. The following requirements apply only to the 1440-SDM02-
01RA module. See the user manual for the specific XM module for its
requirements and
Additional Resources on page 11
The XM-124 module is designed so that it can be used to replace an XM-120
or XM-121 module, revisions D01 or later. If an earlier revision of an XM-120/
XM-121 module is being replaced, changes to wiring can be required. See
the XM-120/XM-121 User Manual for details.
If replacing an XM-120/XM-121 module with which the XM-120/X-121
onboard relay is being used, be sure that the relay requirements and wiring
solution are considered, as differences exist between the onboard relays of
the XM-120/XM-121 and the XM-124 module.
ATTENTION:
The XM-124 module requires a minimum clearance of 25 mm
(1 in.) from the top and bottom of the device.