Rockwell Automation Publication 1440-UM001D-EN-P - September 2016
35
Install the XM-124 Standard Dynamic Measurement Module
Chapter 1
Connect the Buffered Outputs
The XM-124 module provides buffered outputs of all transducer input signals.
The buffered output connections can be used to connect the module to
portable data collectors or other online systems.
shows the buffered output connections for the modules.
Figure 14 - Buffered Output Connections
Connect the Transducer
The Transducer Power Type parameter described in
controls the range
of the buffered output signal. The XM-124 module can accept inputs from any
Allen-Bradley non-contact eddy current probe, a standard IEPE accelerometer,
a velocity transducer, AC voltage output, or a DC voltage output measurement
device.
BNC
BNC
Signal 1 Buffered Output
Signal 2 Buffered Output
Table 4 - Transducer Power Type
Transducer Power Setting
Buffered Output Range
Off
-12V…12V
IEPE
0V…24V
24V
0V…24V
-24V
-24V …0V
Bias Current
-12V…12V