Rockwell Automation Publication 1440-UM001D-EN-P - September 2016
61
Install the XM-124 Standard Dynamic Measurement Module
Chapter 1
• The ADR and trigger group functions cannot be used together. A
module can have only one primary master so a module cannot be both
configured for ADR and included in a trigger group. The ADR scanner
must be the primary master for the modules configured for ADR. The
XM-440 Master Relay module must be the primary master for modules
included in a trigger group.
Power Up the Module
The module performs a self-test at powerup. The self-test includes a status
indicator test and a device test. During the status indicator test, the indicators
are turned on independently and in sequence for approximately 0.25 seconds.
The device test occurs after the Status Indicator test. The Module Status (ms)
indicator is used to indicate the status of the device self-test.
ms Indicator State
Description
Flashing Red and Green
Device self-test is in progress.
Solid Green or Flashing Green
Device self-test completed successfully, and the firmware
is valid and running.
Flashing Red
Device self-test competed, the hardware is OK, but the
firmware is invalid, the firmware download is in progress,
or, the node address or communication rate DIP switch
settings have been changed and do not match the
settings in use.
Solid Red
Unrecoverable fault, hardware failure, or Boot Loader
program may be corrupted.