144
Rockwell Automation Publication 1440-UM001D-EN-P - September 2016
Appendix B
CIP Objects
Instance Attributes
Table 71 - Overall Measurement Object Instance Attributes
Attribute
ID
Access Rule
Name
Data Type
Description
Semantics
3
Get
Overall Value
REAL
Measured value
The output value of the measurement that the
Overall Measurement Object performs on the input
signal. The result of the measurement process that is
specified by Measurement is converted to the units
specified by Data Units to produce the Overall Value.
4
Get
Status
BOOL
Indicates if a fault or alarm has occurred.
0 = Operating without alarms or faults.
1 = Alarm or fault condition exists. The Overall Value
attribute does not always match the actual field
value.
5
Get
Data Units
ENGUNIT
The units context of the Overall Value
attribute.
The Output Data Units attribute for the Channel
Object determine the setting. (see
6
Get/Set
Measurement
USINT
The measurement (or calculation)
performed to produce the Overall Value.
0 = RMS
1 = RMS peak
2 = RMS pk-to-pk
3 = Peak
4 = Peak-to-peak
5…255 Reserved
7
Get
Time Constant
REAL
The detection time constant that is
associated with the output smoothing filter
(for the RMS and DC meters) or the decay
rate of the peak meters.
This setting is based on the Low Frequency Cutoff
(Channel object) and Measurement (attribute 6).
If Measurement is set to 3 or 4, the Overall Time
Constant is 1.5 seconds.
If Measurement is set to 0, 1, or 2, this table shows
the Time Constant.
8
Get
Damping Factor
REAL
The damping factor that is associated with
output smoothing filter for the RMS and DC
meters (not used with peak meters).
1.0
9
Get/Set
Overall Filter
USINT
Overall filter type that is applied to the
input signal before the measurement is
performed.
0 = None
1 = Low Pass Filter
2…255 Reserved
10
Get/Set
Low Pass Corner
Frequency
UINT
The corner frequency of the low pass filter.
100…20,000 Hz
Low
Frequency
Cutoff
Overall
Time
Constant
0.2 Hz
0.8
1 Hz
0.16
5 Hz
0.045
10 Hz
0.045
40 Hz
0.045
Summary of Contents for 1440-SDM02-01RA
Page 8: ...8 Rockwell Automation Publication 1440 UM001D EN P September 2016 Table of Contents Notes...
Page 10: ...10 Rockwell Automation Publication 1440 UM001D EN P September 2016 Summary of Changes Notes...
Page 12: ...12 Rockwell Automation Publication 1440 UM001D EN P September 2016 Preface Notes...
Page 167: ......