Rockwell Automation Publication 1440-UM001D-EN-P - September 2016
117
Status Indicators
Appendix A
Channel 1 and Channel 2
Status Indicators
This table describes the channel indicators.
Tachometer Status Indicators
This table describes the tachometer indicator.
Setpoint Multiplier Indicator
This table describes the setpoint multiplier indicator.
State
Probable Cause
Off
• Normal operation within alarm limits on the channel.
• No power applied to the module. Examine module status indicator.
Solid Yellow
An alarm that is associated with this channel is in Alert.
Solid Red
An alarm that is associated with this channel is in Danger.
Flashing Red
A transducer fault exists on the channel. The DC bias is outside the DC Low
and High Limits.
State
Probable Cause
Off
• Normal operation within alarm limits on the channel.
• No power applied to the module. Examine module status indicator.
Solid Yellow
An alarm on Speed or Acceleration is in Alert.
Solid Red
An alarm on Speed or Acceleration is in Danger.
Flashing Yellow
A tachometer fault other than a transducer fault (for example, no pulse
received).
Flashing Red
The tachometer signal DC bias is not within the DC Low and High Limits.
State
Probable Cause
Off
The Alarm Limit Multiplier is not in effect.
Solid Yellow
The Alarm Limit Multiplier is in effect.