Install the XM-124 Standard Dynamic Measurement Module
Connecting Power
Power that is supplied to the module must be nominally 24V DC (±10%) and
must be a Class 2 rated source.
Wire the DC-input power supply to the terminal base unit as shown in
.
Figure 9 - DC Input Power Supply Connections
37
Chassis
Connection to DIN rail ground spring or panel mounting hole
38
Chassis
Connection to DIN rail ground spring or panel mounting hole
39
SetPtMult
Switch input to activate setpoint Multiplication (active closed)
40
Switch RTN
Switch return, shared between SetPtMult and Reset Relay
41
Reset Relay
Switch input to reset internal relay (active closed)
42
Reserved
43
24 V Common
Internally DC-coupled to circuit ground
44
24 V In
Connection to primary external 24 V power supply, positive side
45
24 V Common
Connection to external 24 V power supply, negative side (internally DC-coupled to
circuit ground)
46
Reserved
47
Relay Common
Relay Common contact
48
Relay N.O.
Relay Normally Open contact
49
Reserved
50
Reserved
51
Reserved
(1) Terminals are internally connected and isolated from the chassis terminals.
IMPORTANT
A Class 2 circuit can be provided by use of an NEC Class 2 rated power
supply, or by using a SELV or PELV rated power supply with a 5 A current
limiting fuse installed before the XM module.
Table 2 - Terminal Block Assignments
No.
Name
Description
+
-
24V DC
power
supply
Power supply
Negative (common)
side must be grounded