46
Rockwell Automation Publication 1440-UM001D-EN-P - September 2016
Chapter 1
Install the XM-124 Standard Dynamic Measurement Module
Figure 27 - Velocity Sensor and Two Non-contact Sensor Wiring
IMPORTANT
Set the Transducer Power Type for channel 2…-24 V so that the buffered
output ranges from -24…0 Volts.
22
Pin A - Common
Pin B - Signal
Cable shield not
connected at this end
Shield
Channel 1 Input Signal
Signal Common
Signal Common
Channel 2 Input Signal
-24V DC*
-24V DC
Signal Common
Tach Input Signal
13
Shield
Shield
31
22
4
1
0
21
20
18
17
16
36
TYPICAL WIRING FOR COIL-BASED VELOCITY SENSOR AND TWO
NON-CONTACT SENSORS TO XM-124 STANDARD DYNAMIC MEASUREMENT MODULE