40
Rockwell Automation Publication 1440-UM001D-EN-P - September 2016
Chapter 1
Install the XM-124 Standard Dynamic Measurement Module
Figure 20 - Velocity Sensor to Channel 2 Wiring
Connect a Powered Sensor
Figures
and
show the wiring of a powered sensor, such as the Model 580
Vibration Pickup, to the terminal base unit.
Pin A - Common
Pin B - Si gn al
Cabl e s hiel d not
conn ecte d at thi s end
Shield
1
17
Channel 2 Input Signal
Signal Common
38
TYPICAL WIRING FOR COIL-BASED VELOCITY SENSOR
TO XM-124 STANDARD DYNAMIC MEASUREMENT MODULE CHANNEL 2
ATTENTION:
You may ground the cable shield at either end of the
cable. Do not ground the shield at both ends. Recommended practice
is to ground the cable shield at the terminal base and not at the
transducer. Any convenient chassis terminal may be used.
See
Terminal Block Assignments on page 28
IMPORTANT
Set the channel Transducer Power Type to 24V so that the buffered output
ranges from 0 Volts to 24 Volts.