Rockwell Automation Publication 1440-UM001D-EN-P - September 2016
67
Configure the XM-124 Standard Dynamic Measurement Module
Chapter 2
Configuring the XM-124
Standard Dynamic
Measurement Module
The editor for the XM-124 standard dynamic measurement module follows
the same style and design as the editors for other XM modules. Each tab
presents a dialog box that contains related parameters.
Generally, a module is configured from the leftmost tab, working toward the
right. Begin the XM-124 module configuration with the Channel tabs.
Configure the Channel Properties
Use the Channel tab to define the characteristics of the transducer and the
signal processing that is performed on the input signals. The XM-124 module
has two input channels.
1. From the Module Properties dialog box, click the Channel tab.
2. Configure the parameters as necessary.
Transducer
Table 7 - Transducer parameters
In this field
Values are
Comments
Channel Name
Enter a descriptive name for the channel.
Maximum 18 characters.
Power
Choose the type of power that is supplied to the transducer:
• Off
• IEPE (externally supplied)
• -24V (externally supplied)
• 24V (externally supplied from the terminal base)
• Bias Current (externally supplied)
See Connect the Transducer on page 35
requirements.
See
Transducer Power Settings on page 69
to view more
details for each setting.