148
Rockwell Automation Publication 1440-UM001D-EN-P - September 2016
Appendix B
CIP Objects
Instance Attributes
Table 76 - Spectrum Waveform Measurement Object Instance Attributes
Attribute
ID
Access
Rule
Name Data
Type
Description
Semantics
3
Get
Status
BOOL
Indicates if a fault or alarm has occurred.
0 = Operating without alarms or faults.
1 = Alarm or fault condition exists. The Spectrum and
Waveform data does not always match the actual field
value.
4
Get
Data Units
ENGUNIT
The units context of the
Data
attributes.
This setting is determined by the Output Data Units
attribute for the Channel Object.
See
.
5
Get
Domain
USINT
The domain that is used for the spectrum and
waveform measurements.
0 = Frequency/Time
1 = Order/Position
6
Get/Set
FMAX
REAL
The maximum frequency or order of the spectrum
data.
0…20,000 Hz if Domain = 0. There are several
predetermined FMAX settings for which spectrum
data can be produced. If you select an unsupported
value, then the next greater supported FMAX value is
used for the spectrum data.
4…40 Orders if Domain = 1.The Number of Lines
value must be evenly divisible by the FMAX value or
an Invalid Device Configuration error is returned
during the Device Mode Object Start and Save
services.
7
Get/Set
Number of Spectrum
Lines
UDINT
Number of lines or bins in the spectrum data.
100, 200, 400, 800, or 1600
8
Get/Set
Window Type
USINT
The window function to be applied to the waveform
data before computing the spectrum.
0 = Rectangular
1 = Hamming
2 = Hanning
3 = Flat Top
4 = Kaiser Bessel
9
Get/Set
Period
REAL
The period of the waveform.
Seconds if Domain = 0.
Cycles if Domain = 1.
10
Get
Number of Waveform
Points
UDINT
Number of points in the waveform data.
256, 512, 1024, 2048, or 4096
11
Get
Overlap
USINT
The percent overlap applied to the waveform data sets
used for calculating the spectrum.
Only 0% supported.
12
Get/Set
Data Format
USINT
The format of the spectrum data.
0 = Complex data
1 = Magnitude data
13
Get
Average Type
USINT
The type of averaging performed.
0 = Asynchronous (spectrum)
1 = Synchronous (waveform)
• Determined by the Synchronous attribute of the
Channel Object.
• When set to Asynchronous, consecutive spectrum
measurements are averaged together to produce
the Spectrum data.
• When set to synchronous, synchronized
waveforms are averaged together to produce the
Waveform data, and the Spectrum data is
produced from the averaged waveform. A trigger
source from a tachometer, for example, is required
to obtain the synchronized waveforms.