Rockwell Automation Publication 1440-UM001D-EN-P - September 2016
21
Install the XM-124 Standard Dynamic Measurement Module
Chapter 1
Figure 4 - XM System DIN Rail Grounding
Panel/Wall Mount Grounding
The XM modules can also be mounted to a conductive mounting plate that is
grounded, as shown in
. Use the grounding screw hole that is provided
on the terminal base to connect the mounting plate to the Functional Earth
terminals, as shown in
.
DYNAMIC MEASUREMENT
1440-VST02-01RA
DYNAMIC MEASUREMENT
1440-VST02-01RA
POSITION
1440-TSP02-01RB
MASTER RELAY
1440-RMA00-04RC
EXPANSION RELAY
1440-REX00-04RD
EXPANSION RELAY
1440-REX00-04RD
EXPANSION RELAY
1440-REX00-04RD
EXPANSION RELAY
1440-REX00-04RD
DYNAMIC MEASUREMENT
1440-VST02-01RA
DYNAMIC MEASUREMENT
1440-VST02-01RA
EXPANSION RELAY
1440-REX00-04RD
EXPANSION RELAY
1440-REX00-04RD
AC in
AC in
Use 2.1 mm
2
(14 AWG) wire
Use 8.4 mm
2
(8 AWG) wire.
Use 8.4 mm
2
(8 AWG) wire.
Ground bus
Grounding - Electrode
Conductor to Grounding-Electrode System
24V COM
24V
24V COM
24V
24V COM
24V
Power
Supply
Power
Supply