
Rockwell Automation Publication 1440-UM001D-EN-P - September 2016
19
Install the XM-124 Standard Dynamic Measurement Module
Chapter 1
Power Requirements
Before you install the module, calculate the power requirements of all modules
that are interconnected via their side connectors. The total current draw
through the side connector cannot exceed 3 A. See the specifications for the
individual module for power requirements.
.
is an illustration of wiring modules using separate power connections.
Figure 2 - XM Modules with Separate Power Connections
Table 1 - Power Supply Requirements
ATTENTION:
A separate power connection is necessary if the total current
draw of the interconnecting modules is greater than 3 A.
Any limited power source that satisfies
the power requirements
XM Power Supply Requirements
Protection
Listed Class 2 rated supply
Fused
(1)
ITE Listed SELF supply
Fused
(1)
ITE Listed PELV supply
Output Voltage
24V DC ± 10%
Output Power
100 W max (~4 A @ 24V DC)
Static Regulation
±2%
Dynamic Regulation
±3%
Summary of Contents for 1440-SDM02-01RA
Page 8: ...8 Rockwell Automation Publication 1440 UM001D EN P September 2016 Table of Contents Notes...
Page 10: ...10 Rockwell Automation Publication 1440 UM001D EN P September 2016 Summary of Changes Notes...
Page 12: ...12 Rockwell Automation Publication 1440 UM001D EN P September 2016 Preface Notes...
Page 167: ......