Invalid Configuration Errors
A Start or Save service request to the XM-124 module can return an Invalid
Device Configuration error when there is a conflict among the configuration
settings.
The general error code for the Invalid Device Configuration error is D0
hex
. An
additional error code is returned with the general error code to specify which
configuration settings are invalid.
lists the additional error codes that
are associated with the Invalid Device Configuration error.
XM-124 Module I/O Message
Formats
The XM-124 standard dynamic measurement module supports Poll, Change
of State (COS), and Bit-Strobe I/O messages. The Poll response message is
used by the module to produce measured values, and the COS message is used
to produce the Alarm and Relay Status. The Bit-Strobe message is used by a
master device to send a trigger event to the XM slaves on the network.
Table 23 - Additional Error Codes returned with the Invalid Device Configuration Error (0xD0)
Error Code
(Hex)
Description
01
No specific error information is available.
02
Mismatched transducer, channel, and/or measurement unit.
03
Inverted transducer fault high/low values.
04
Alarm thresholds conflict with the alarm condition.
05
Alarm speed range is invalid.
06
Band minimum frequency is greater than maximum frequency. Or, maximum frequency is
greater than FMAX.
07
Relay is associated with an alarm that is not enabled.
08
Tachometer must be enabled for alarm or channel settings.
09
A senseless speed range is enabled on a speed alarm.
0A
Too many alarms are associated with one measurement.
0B
Invalid node address in the alarm list.
0C
Too many alarms in the alarm list. Or, no alarms in the alarm list.
0D
Alarm levels cannot be zero for alarms that are enabled.
0E
Too many slaves in the scanner input data table.
0F
The FMAX and Number of Lines do not yield correct vector calculations.
10
Phase (vector) alarms prohibited with synchronous sampling and multiple tachometer pulses
per revolution.
11
Can’t have order-based band on asynchronous channel.
12
Unsupported Sensor Type and Channel ID combination.
13
Invalid Alarm Type for the associated measurement ID.
14
Synchronous sampling is required for alarm on synchronous measurements.
15
Integration is not supported with the Bypass High Pass Filter option.