24
HydroSens
4.9
HydroSens™
HydroSens InRoom
HydroSens AHU
Flow l/h
4-600
24-800
84-1200
4-600
24-800
84-1200
Power supply
230/240 V, 50/60 Hz is always 1P+N+PE
230/240 V, 50/60 Hz. 16 Amp
1P+ N + PE
3x400/230 to
480/240 V, 16 Amp
3P + N + PE
230/240 V, 50/60 Hz. 16 Amp
1P+ N + PE
3x400/230 to
480/240 V, 16 Amp
3P + N + PE
Max load power output kw
1,8
1,8
5
1,8
1,8
5
Frequency inverter kw
1,5
2,2
1,5
2,2
Ventilator supply
Max. 10 Amp available
Note the effect demand from total amount of atomizers
Max. 10 Amp available
Note the effect demand from total amount of atomizers
Supply water pressure bar/psi
2-7 / 29-101,5
2-7 / 29-101,5
Supply water connection Ø
14
14
Sensor control
0-10 V
0-10 V / BMS 0-10 V PID
On/off control
Control
4/8/10 zones humidity or 2/4/5 zones humi./temp.
2/3 AHU
Pulsing function
/
Not with fan start/stop
Hygienic rinse system
Ethernet/MODBUS TCP
microSD slot
4-32 Gb SDSC or SDHC class 6 or 10
4-32 Gb SDSC or SDHC class 6 or 10
Datalog
(microSD card required)
(microSD card required)
Maintenance indicator
External stop
1 input available to stop 1 or more zones
Seperate input to allow AHU operation
Alarm log
Alarm out, potential free
External alarm in
1 input available to stop system in alarm, reset required
Thermal pump control
Flow control
Low water pressure alarm
High/low humidity alarm
Dimensions (width x depth x height)
590 x 365 x 1030 mm / 23,2” x 14,4” x 40,5”
590 x 365 x 1030 mm / 23,2” x 14,4” x 40,5”
Weight kg/lbs
53 / 116,8
56 / 134,5
65 / 149,9
53 / 116,8
56 / 134,5
65 / 149,9
Ambient temperature range °C/°F
1-20 (35) / 34-68 (95)
1-20 (35) / 34-68 (95)
Protection class IP
52
52
Noice level , dB (A)
< 70
< 70
VDI 6022 compliant
Ventilator start/stop
Option
Scada remote control
Option
Option
MODBUS RTU (RS232/485)
Option
Option ( then analog input 4-20 mA is not optional)
Analog input 4-20 mA
Option (then MODBUS RTU is not optional)
201218