75
Alarm screens
Alarm 1
-ALARM-
No Water
External
Temp. Motor
Fault K1 Start
Fault K1 Stop
Alarm 2
-ALARM-
Low Prod. Flow
Low Drain Flow
Information that an alarm i active:
Only active alarms is shown, if there are no alarms then the alarm
screen will not be visible.
For more information, go to section 11 - troubleshooting.
Flow calibration screen
Flow calibration
Flow Calibration
Production (RO)
1000
Drain
1000
Calibrate the flow sensors:
Production
Drain
Calibration value for production.
Calibration value for drain.
Before calculating new calibration value, set prod and drain to 1000.
Measure the production and drain flow, calculate to l/h.
Read the flow in the display.
Calculate the calibration value, and enter it in the display
(only integer)
How to calculate:
201218