14
Hydrosens for InRoom application:
Our high pressure pump and control unit, is designed to supply water to nozzle atomizers at a constant pressure to multiple rooms or steps, constantly
adapting to variable flow conditions.
During this process the control is monitoring that all conditions are within the operational spectra, to obtain and maintain operational stability and
safe operation.
The pump starts and activates a specific zone valve. When the setpoint is reached, the zone valve deactivates, closing operation mode and activating
drain mode to relieve the pressure from the nozzle fast to prevent dripping.
The drain line will retain a pressure of 2,5 bars in the hoses in standby condition. This keeps air out of the pipes ensuring instant atomization from the
nozzles when starting up.
Atomizer:
Atomizing is done from an atomizing unit with a certain amount of nozzles or from a flexible “nozzle in a line“ installation.
The single nozzle can be applied in different capacity range depending on needs, installation and ambient conditions.
Sensor:
The position of the sensor is determinating the control feedback signal to the Hydrosens. It is therefore important to position the sensor correct.
Hydrosens with AHU application:
Our high pressure pump and control unit, is designed to supply water to the air handeling unit´s spray chamber, at a constant pressure constantly
adapting to variable flow conditions.
The control setup makes it possible to adjust the output to be almost 100% linear.
During this process the control is monitoring that all conditions are within the operational spectra, to obtain and maintain operational stability and
safe operation.
The output is controlled by multiple solenoid valves.
This is controlled by 2 control loops:
1. The wanted setpoint from the room/BMS system.
2. The output from the humidification champer.
The PI control is ensuring that maximum saturation and minimum waste is present during operation.
AHU pads:
Our glaspads are designed to ensure the most efficiency saturation of the air, and obtain as close to 100% of the atomized water to minimize waste.
The pads retain water droplets to the humidification chamber.