ScreenMaster RVG200
Paperless recorder
7 Configuration
OI/RVG200-EN
103
Tag/Units
Tag
Enter the totalizer tag to be displayed in the Indicator view and the
Totalizer log (6 characters maximum).
Refer to Appendix F, page 180 for further information regarding character
use in tags.
Units
Select any of the totalizer units pre-programmed into the recorder or
select
Custom
and enter user-defined units (6 characters maximum).
Refer to Appendix D, Table D.2, page 172 for a description of the
pre-defined totalizer units.
Note.
The recorder can be configured to calculate the totalizer count rate
automatically by ensuring that the engineering range unit of measurement
selected for the channel to which the totalizer is assigned is a volumetric
unit (quantity per unit of time, for example, gallons per hour) – see
page 92. If the recorder holds the relationship data between the selected
engineering range unit of measurement (see page 92) and the selected
totalizer units, the totalizer count rate (see page 106) is calculated and
displayed automatically.
Stop/Go/Reset
Select the totalizer action following a power failure and a digital signal to
stop and start the totalizer:
Stop/Go recovery
Last
Stop
Go
–
–
–
on power recovery, the totalizer continues in the same state as
before the failure, either stopped or running.
totalizer stops counting.
totalizer starts counting from the last recorded value.
Stop/Go source
Select a signal source to stop and start the totalizer; Refer to Appendix A,
page 146 for a description of the available sources.
Note.
This signal is edge-triggered. A rising edge (inactive to active) starts
the totalizer. A falling edge (active to inactive) stops the totalizer.
Reset source
Select a signal source (see Appendix A, page 146) – an edge-triggered
signal to reset the totalizer on a rising edge.
Timed Reset
Set the days and time at which the totalizer is reset.
Start
Stop