ScreenMaster RVG200
Paperless recorder
Appendix E – Batch recording
178
OI/RVG200-EN
E.3.3 Batch configuration
To configure batch recording, access Process Group Configuration (see Section 7.8, page 80), select the
required Process Group and select the
Batch
tab. Exit and save the configuration when complete.
Batch
Enable Batch Recording
Enable Batch Recording
Set to
On
to enable batch recording for the selected process group.
Note.
The following parameters are displayed only if
Enable Batch Recording
is set to
On
.
Batch Type
Touch
to toggle between
Standard
and
Concurrent
.
Start/Stop, Abort
Start/Stop Batch Source
Select a digital signal source to start batch recording on a rising edge and
stop batch recording on a falling edge.
Note.
If
Batch Number
(see next page) is set to
Off
or
Text
and a batch is
started using a digital signal, the contents of the
Batch Number
and
batch identification fields (if configured – see next page) are copied
automatically to the new batch. If
Batch Number
is set to
Automatic
, the
content of the
Batch Number
field is incremented by one, automatically.
Batch Power Failure
Select a time between 1 minute and 2 hours to enable this function or
select
Off
to disable it.
If this function is enabled and electrical power is lost for more than the
time selected, the batch is stopped and a digital
Batch Power Failure
signal
is activated for 5 seconds.
Note.
The value selected affects all groups. The default value is
Off
.
Operator Login
Select the type of batch recording security required:
Start
Start and
Stop
Disabled
–
–
–
the operator is required to enter a password to start
batch recording.
the operator is required to enter a password to start
and stop batch recording.
batch recording security is disabled.
Note.
Batch recording security can be enabled only if
Security system
is
set to
Advanced
(see Section E.3.1, page 177), If
Security system
is
set to
Basic
this parameter is set automatically to
Disabled
and the
edit button is not displayed.
If this parameter is set to
Disabled
no security is required to start or
stop batch recording and the operator name is not displayed.