ScreenMaster RVG200
Paperless recorder
Appendix B – MODBUS TCP / MODBUS 485
160
OI/RVG200-EN
B.5 Operating mode MODBUS registers
Tables B.12 to B.14 detail the contents of the MODBUS TCP registers accessible while the recorder is in
the operating mode.
Two data types are used:
32-bit single precision floating point data in IEEE format
64-bit double precision floating point data in IEEE format
Note.
When writing to a parameter that occupies more than one register position, all registers relating to
that parameter MUST be written to as part of a multiple register write. If this is not achieved a NAK
exception response is issued. Individual registers can be read without causing an exception
response.
When accessing a parameter that occupies more than one register position, the lowest numbered
register contains the most significant data.
Read only, IEEE floating point 32 bit number
Module
A
MODBUS
register
Module
B
MODBUS
register
Module
C
MODBUS
register
Module
D
MODBUS
register
A1
0001 and 0002
B1
0013 and 0014
C1
0025 and 0026
D1
0037 and 0038
A2
0003 and 0004
B2
0015 and 0016
C2
0027 and 0028
D2
0039 and 0040
A3
0005 and 0006
B3
0017 and 0018
C3
0029 and 0030
D3
0041 and 0042
A4
0007 and 0008
B4
0019 and 0020
C4
0031 and 0032
D4
0043 and 0044
A5
0009 and 0010
B5
0021 and 0022
C5
0033 and 0034
D5
0045 and 0046
A6
0011 and 0012
B6
0023 and 0024
C6
0035 and 0036
D6
0047 and 0048
Table B.12 Analog inputs
Read / Write, IEEE floating point 32 bit number
Alarm
MODBUS
registers
Alarm
MODBUS
registers
Alarm
MODBUS
registers
Alarm
MODBUS
registers
1A
101 and 102
7A
149 and 150
13A
197 and 198
19A
245 and 246
1B
103 and 104
7B
151 and 152
13B
199 and 200
19B
247 and 248
1C
105 and 106
7C
153 and 154
13C
201 and 202
19C
249 and 250
1D
107 and 108
7D
155 and 156
13D
203 and 204
19D
251 and 252
2A
109 and 110
8A
157 and 158
14A
205 and 206
20A
253 and 254
2B
111 and 112
8B
159 and 160
14B
207 and 208
20B
255 and 256
2C
113 and 114
8C
161 and 162
14C
209 and 210
20C
257 and 258
2D
115 and 116
8D
163 and 164
14D
211 and 212
20D
259 and 260
3A
117 and 118
9A
165 and 166
15A
213 and 214
21A
261 and 262
3B
119 and 120
9B
167 and 168
15B
215 and 216
21B
263 and 264
3C
121 and 122
9C
169 and 170
15C
217 and 218
21C
265 and 266
3D
123 and 124
9D
171 and 172
15D
219 and 220
21D
267 and 268
Table B.13 Alarm trip values