ScreenMaster RVG200
Paperless recorder
7 Configuration
OI/RVG200-EN
67
Note. 1
Changes are saved to persistent storage only when
Apply Changes
or
Export Configuration
is
selected. Any powerdown before this results in lost configuration changes.
If
Apply Changes
is selected, new internal data files for enabled recording channels are created if:
– A recording channel source parameter is changed
– The primary and / or secondary sample rates and / or their sources for either process group are
changed.
– The input filter type parameter for any channel is changed
– the engineering range parameter for any channel is changed
– A channel tag parameter is changed
– The number of process groups is changed
– A previously disabled channel is enabled
Touching
suspends recording briefly while the new configuration is implemented.
Note. 2
If changes are made to the current configuration and
Export Configuration
is selected, the
configuration file complete with changes is saved to the selected storage media but the recorder
continues to use the current, unchanged configuration. To make an exported configuration the current
configuration:
1.
Access the
Configuration
level – see Section 7.3, page 60.
2.
Open the saved configuration – see see Fig. 7.2, page 61.
3.
Touch
to exit the
Configuration
level.