ScreenMaster RVG200
Paperless recorder
7 Configuration
OI/RVG200-EN
119
7.10.5 Email
The recorder can be configured to send emails to a maximum of 6 recipients in response to certain events.
The addressees can all subscribe to the same SMTP server or the recorder can be configured to send
emails via 2 different SMTP servers to a maximum of 3 addressees per server.
Up to 10 independently configurable triggers can be enabled to generate an email when the selected
source becomes active.
When a trigger source becomes active, an internal 1 minute delay timer is started. At the end of that
minute, an email is generated that includes, not only the event that initiated the delay timer, but every other
event that occurred during the delay period together with any enabled reports. The data returned in the
email therefore reflects the real-time alarm state at the time the email was generated, not the state when the
first trigger source became active.
Each email includes a link to the recorder's embedded web server enabling the recorder's data and status
to be viewed remotely using an internet browser on a PC.
Auto Address
Touch
to toggle between
Enabled
and
Disabled
.
Set to
Disabled
if the sender address must contain a domain literal
address (for example, the recorder's IP address) and enter the address in
the
Sender Address
field (below).
Select
Enabled
if the sender address must be a domain name.
Sender Address
Note.
Displayed only if
Auto Address
is set to
Disabled
.
Enter the address of the email sender.
Note.
The address must contain a valid domain name.
.