7 Configuration
OI/RVG200-EN
115
7.10.3 Hybrid modules
Output C1
(to D6)
Output Mode
Select the output mode required –
Analog
,
Digital
or
TxPSU
.
Note.
The following parameter is displayed only if
Output Mode
is set to
Analog
or
Digital
.
Source
Select the output source required.
An analog output source is the internal analog signal used to generate the
analog output signal.
A digital output source is the internal digital source used to activate /
de-activate a digital output.
Note.
If a digital output is used to provide a totalizer count pulse, the
maximum pulse frequency is 1 Hz.
Note.
The following parameters are displayed only if
Output Mode
is set to
Analog
.
Engineering low
Engineering high
Set the required analog output engineering range.
Note.
These settings are the engineering values corresponding to the
Electrical low
and
Electrical high
values below.
Electrical low
Electrical high
Set the required analog output electrical range.
These values are the minimum and maximum values of the current output,
in electrical units – range 0 to 23 mA.
Note.
The following parameter is displayed only if
Output Mode
is set to
Digital
.
Polarity
Select the digital output source polarity.
Note.
When set to
Positive
, the digital output is energized when the
digital source is active (On).
Analog output
engineering high
Analog output
engineering low
Analog output
electrical high
Analog output
electrical low
Source range high
Source range low